FV563 Rev.  -  12/2/14

Page 9

OPERATION

1.) Invisible light rays are continually emitted from the faucet
sensor.

2.) When the user’s hands come into range of  the sensor’s
detection zone (factory set at approximately 6”), the beam is
reflected back to the sensor’s reciever and converted to a low
voltage electrical  signal  activating a solenoid valve.

3.) After the user removes their hands, the absence of reflected
light stops the low voltage electrical signal, closing the valve.
The circuit automatically resets for the next user.

4.) If an object is in view continuously for thirty seconds, the
faucet will automatically shut off. The faucet will remain off until
the object is removed.  After the object is removed, the faucet
functions normally.

Aqua-FIT

TM

 is a trademark of Zurn Industries, LLC.

Printed in the U.S.A.

TROUBLESHOOTING GUIDE

SPECIFICATION

Voltage:

Sensor Range:

Operating Water
Pressure:

Ambient
Temperature:

Operational Water
Temperature:

Aerator:

6 VDC
(4 “AA” Alkaline)

6” Approximate from Water Outlet

20-80 psi

32ºF to 122ºF (0ºC to 50ºC)

35°F to 140°F (2°C to 60°C)

1.5 GPM Vandal-Resistant (Standard)

ZURN INDUSTRIES, LLC. 

 COMMERCIAL BRASS OPERATION 

 5900 ELWIN BUCHANAN DRIVE 

 SANFORD NC 27330

Phone: 1-800-997-3876 

 Fax: 919-775-3541 

 World Wide Web: www.zurn.com

In Canada: ZURN INDUSTRIES LIMITED 

 3544 Nashua Drive 

 Mississauga, Ontario L4V1L2 

 Phone: 905-405-8272 Fax: 905-405-1292

POTENTIAL SITUATIONS

POSSIBLE CAUSES

SUGGESTED SOLUTION TIPS

Solenoid is not connected properly

Place hands in sensor range. If clicking occurs, solenoid is connected 
correctly. If no clicking occurs, disconnect the sensor cable from the 
black box and w ait 15 sec bef ore reconnecting. Once reconnected try 
activating again. 

Batteries are low  on pow er

Change out batteries

Sensor and electronic connector cable has 
bent or broken pins

Check to see if pins are missing, bent, or broken. If  yes, then the 
electronic box needs replaced

Solenoid is lodged w ith debris

Check solenoid for debris and clean if necessary and reassemble

If  f aucet is hardw ired, could have voltage 
range issues

Check voltage levels and adjust if necessary to f all w ithin 
recommended ranges.

Sensor lens could be obstructed by 
environmental factors such as high ref lective 
surf aces or bright lighting conditions

If this is the case, then adjust the dip sw itch settings f or sensor 
resolution per the diagram in the installation manual (sw itches 7 and 8)

Sensor lens could have surface damage, 
scratches, or deposit build ups f rom chemical 
cleaners

Inspect the sensor lens underneath the spout tip.  May require cleaning 
(damp rag) or replacement

Remove the battery tray and inspect for visual signs of rust, w ater, 
debris. Replace battery tray if these symptoms are f ound. 
Remove battery tray, if no visual signs can be detected, try using a 
metallic object to tap the coils to exhaust any fault charges. Reassemble 

Sensor f aucet does not 
activate af ter initial installation

Sensor lens may not have had enough time to 
calibrate prior to a user or target trying to 
initiate activation

Disconnect the sensor and electronic box cables and w ait for 15 
seconds. Reconnect the cables, but allow  f or another 15 seconds 
before placing hands or a target w ithin the sensor range. Y ou should 
hear a click of  the solenoid once calibration is complete.

Solenoid is lodged w ith debris

Check solenoid for debris and clean if necessary and reassemble

Sensor and electronic connector cable has 
bent or broken pins

Check to see if pins are missing, bent, or broken. If  yes, then the 
electronic box needs replaced

If this is the case, then adjust the dip sw itch settings f or sensor 
resolution per the diagram in the installation manual (sw itches 7 and 8)
Loosen the mounting nuts and try sliding the f aucet back in the lavatory, 
sink, or counter top holes back tow ards the w all and retightening. Could 
be detecting the grid drain in the sink bow l.

Mounting hardw are is not tightened suf ficiently 
(faucet shank, electronic box, supply hoses, 
etc)

Check and ensure the nuts and joints are tight and secure from the 
supply stop all the w ay to the f aucet shank.

Missing the w asher located in the solenoid box 
nut w here it assembles to the f aucet shank.

Make sure w ater supply stops are shut of f. Check to ensure the 
w asher is installed. If not, need to replace w ith a new  w asher.

Sensor f aucet is leaking 
underneath the sink or 
counter

Sensor f aucet is not 
activating or running

Coils in battery tray are promoting a voltage 
drain

Faucet runs continuously 
(longer than the selected time-
out that is programmed)

Sensor f aucet is experiencing 
random activations w hen a 
user or target is not w ithin 
sensing range

Sensor lens could be obstructed by 
environmental factors such as high ref lective 
surf aces or bright lighting conditions

Содержание Aqua-FIT Serio Series

Страница 1: ... replacement of the defective goods Before installation and use the purchaser shall determine the suitability of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantab...

Страница 2: ...lation Non toothed Wrench Phillips Head Screwdriver Allen Wrench M3 Allen Wrench 3 32 If you are replacing an existing faucet or Aqua FITTM shells turn off water supply and remove the old faucet Clean lavatory rim around the mounting area for the new sensor faucet Serio SeriesTM Faucets 3a Electronics Box with Solenoid Z6950 55 XL 3b Electronics Box with Solenoid Z6950 XL IM 4 Aerator and Key 5 Mo...

Страница 3: ...with CP4 or CP8 suffix 1 1b Pass sensor connector and shank through cover plate and fasten to the faucet with the provided screws Step 1 Spout Installation 3 4 Shank Gasket Black Box Hex Nut 5 Shank Gasket Black Box Assembly Hex Nut IMBATTERY BOX 2 3 Ensure that arrows are aligned for all connections 6 Step 2 Electronics Module Installation 2 1 Attach electronics module to the shank using the hex ...

Страница 4: ... the supplied solenoid Y connector is connected so that both solenoids will recieve power 9 Step 3 Filter or Mixing Tee or Mixing Valve Installation The supplied inlet filter must be used with every faucet unless a mixing tee or mixing valve is ordered 7 3 2 The optional mixing tee assembly MT or mixing valve MV have integral filters and back checks These take the place of the standard inlet filte...

Страница 5: ...installing an IM model make certain that the supplied solenoid Y connector is connected so that both solenoids will recieve power 13 SET SCREW SIDE SPRING LOCK SIDE Before removing the spout be sure to disconnect the sensor cable below the deck so that the cable head can be pulled up through the deck Note location of set screw and spring lock 17 15 INLINE CONNECTOR CWB HW6 MJ HW6 SOLENOID Y CONNEC...

Страница 6: ...river to remove the screws on both sides of the black box With screws removed the black box can slide off and allow access to the solenoid for service Accessing the Solenoid Use supplied 3 32 hex wrench to loosen set screw Screw will retract into the base to eliminate loss Using the same hex wrench depress the ball detent to release spout from base Lift spout and pull sensor cable through deck and...

Страница 7: ...5 60 20Minutes Off On Off On Off On Off Off On On Off Off Off Off Off Off On On Mode Select Sensing Mode Metering Mode Off On Sensor Resolution 30 20 10 Normal Off On Off On Off Off On On All switches shown in default mode 1 2 3 4 5 6 7 8 ON OFF Sensor Detects Hands and water Turns SensingMode Handsare placed in frontof Sensor WaterTurns On Hands removed fromfront ofSensor WaterTurnsOff Water will...

Страница 8: ...dle Screw for Z6950 XL IM model P6950 XL OS 5 4 Cast Cover Plate w Gasket P6950 CP4 Description 6 8 Cast Cover Plate w Gasket P6950 CP8 7 Z6950 Sensor Assembly P6950 XL EL 8 Mounting Kit P6900 43 9 Filter Kit P6900 120 10 Filter Screen P6900 MV 7 11 Mixing Valve w Filter P6900 XL MV 12 Mixing Tee w Filters and Back Checks P6900 XL MT 13 Optional Plug in Power Converter P6900 ACA 14 Single Stainles...

Страница 9: ...hen adjust the dip sw itch settings for sensor resolution per the diagram in the installation manual sw itches 7 and 8 Sensor lens could have surface damage scratches or deposit build ups from chemical cleaners Inspect the sensor lens underneath the spout tip May require cleaning damp rag or replacement Remove the battery tray and inspect for visual signs of rust w ater debris Replace battery tray...

Отзывы: