ZDAS-16CA SERIES PROGRAMMING GUIDE
--------------------------------------------------------------------------------------------------------------------------------------------------------
PAGE
6
OF 19
TEL2 should be connected to the telephone.
2.6 Connection of Sound Monitor
Sound Monitor Port: The signal line should be connected to MIK, the POSITIVE should be
connected to MIK+, and the negative should be connected to ground wire GND.
2.7 Installation of Keypad
2.7.1 Opening of the keypad: use a screwdriver to open the plastic hole of the back cover upside of
the keypad.
2.7.2 Connection of the keypad: SEE PICTURE,
use a copper core wire to connect the keypad
with connector of alarm panel. The wire from
the keypad to alarm panel is up to 150 meters,
4 keypads can be connected in series; to avoid
destroy of keypad, the anti temper port could be
connected to the terminal of alarm panel.
2.7.3 Keypad address: no address jumper means NO. 1 keypad; insert address jumper “1” means
NO. 2 keypad; insert address jumper “2” means NO. 3 keypad; insert address jumper “1” “2”
means NO. 4 keypad.
2.7.4 Close the cover when the connection is finished.
2.8 Installation when wireless zones only
(only for ZDAS-16CA-8/16/16G)
If you want to use the wireless zones only, connect the wired zones with GND by 2.7K resistors in
short connection, keep close of the wired zones.
Note: Make sure all the connections are correct before power up the alarm panel. Avoiding any
opposite connection, short connection of power line, siren line and detector power line; avoiding
short connection of detector power line and signal line!