Control section which is identical for all MODACT MOK actuators, Types MOK 125 to MOK 1000 type no., with the 

only exception that, it differs in angular displacement of units on the base plate. In the actuator, Type No. 52 325, the unit of 
position-limit signalling switches is arranged as shown in Fig 1. The control section 

(Fig.1)

 consists of position-limit switching 

unit 1, resisence position transmitter 2, torque-limit switching unit 3, terminal block 4 and anti condensation heater 8.

The position-limit switching unit uses 4 microswitches of which 2 are always used for either direction of rotation of the output 

shaft. The switching point of each microswitch can be adjusted independently within the working travel range of the actuator.

The  torque-limit  switching  unit  has  independently  adjustable  microswitches,  one  for  either  direction  of  rotation. 

The torque-limit switches are not secured against opening at the startig torque.

The potentiometer is fitted with a slipping clutch to permit automatic adjustment along with the output shaft.
The anti-condensation heater 8 

(Fig.1, 2)

 prevents water vapours from condensing under the cover of the control 

section. The position-limit switching unit and the position transmitter derive their movements from the output shaft of 
the actuator via a driving gear 

(or in the actuators, Type Nos 52 326 and 52 327, via driving segment 7, as shown in  

Fig. 1).

 The torque-limit switching unit is driven by a “floating worm” of the manual control mechanism where the worm 

displacement is directly proportional to the torque of the actuator output shaft. This enables the actuator to be switched 
off immediately the torque on the output shaft to whichthe torque-limit switching unit has been adjusted, is reached.

Note:  

The microswitches used are of a single-chamber type, i.e., they can operate as a one-pole cut-out switch a contact maker or  
a change-ower switch, whereas the torque-limit switches can be used as cut-out switches only (see the respective circuit layout).

8. ADJUSTMENT OF THE ACTUATOR

a) Stop screws

Stop screws are used to limit the actuator working travel to 90° in compliance with the CLOSED and OPEN end positions of 

the valves having no trip dogs of their own. The screw stops are mounted on the outside of the actuator along with the external 
protective terminal. When viewing the stop screws, the right-hand stop screw is designedfor the CLOSED position, whereas the 
left-hand stop screw is designed for the OPEN position under the assumption that, when viewing the local position indicator, the 
output shaft rotates clockwise in the CLOSE direction of rotation. For adjustment of the stop screws, loosen the stop screws, 
move the actuator with valve into the CLOSED position, and turn the corresponding stop screw till an increased resistance is felt 
when the screw runs onto the stop face within the actuator. Secure the stop screw in position by retightening its lock nut. Then, 
rotate the output shaft of the actuator through a 90° angle to bring it into the OPEN position and set the OPEN-position stop 
screw by the same procedure.

When setting the stop screws in the actuators, Type Nos 52 326 ant 52 327, care should be taken to ensure that,  

in the CLOSED or OPEN end position, the driving gear segment of the position-limit switching and auxiliary signalling 
units cannot strike the electric motor. In either end position of the output shaft of the actuator, the local position indicator 
should tally with the marks on the index plate.

If the valve is required to be tightly closed in the end position and thus the actuator is to be switched off by means of the torque-

limit switches, the tripping torque should be transferred to the valve. In this case, set the corresponding stop screw so that the valve 
is properly sealed when the stops of the output shaft run against the stop screw at which the torque-limit switch operates.

In this case, the respective torque-limit switch is used for switching off the actuator. If stops are required to be used for 

protection of the acutator and the valve against damage in the case of a failure of the position-limit switch set the stop screws 
to such a position which ensures dependable operation of the position-limit switch and is still permissible for the valve. In this 
case, the position-limit switch and the torque-limit switch should be connected in series. Nevertheless, this can only be done 
  when no tight closure of the valve is required.

Legend:

1 –  OPEN torque–limit switch cam
2 –  CLOSE torque–limit switch cam
3 –  OPEN torque–limit switch 
4 –  CLOSE torque–limit switch

5 –  Releasing screw of CLOSE  

torque–limit switch cam

6 –  Releasing screw of OPEN  

torque–limit switch cam

Fig. 3 - 

Torque-limit switches

Содержание MODACT MOK 1000

Страница 1: ...all and Flap Valves 10 18 MODACT MOK 63 t n 52 325 MOK 125 t n 52 326 MOK 250 t n 52 327 MOK 500 t n 52 328 MOK 1000 t n 52 329 MODACT MOK CONTROL MOK 1000 t n 52 329 MOK 1000 t n 52 329 MODACT MOK CO...

Страница 2: ...ZPA Pe ky a s is certified company in accordance with ISO 90001 as amended...

Страница 3: ...flammable and non conductive dust provided that this does not adversely influence their function Here it is necessary to strictly observe SN 34 3205 It is recommended to remove dust as soon as its lay...

Страница 4: ...n is 1200 cycles per hour Mean value of loading torque with load factor 25 and surrounding temperature 50 C is not higher than 40 of maximum tripping torque Mv The highest mean value of loading torque...

Страница 5: ...r supply voltage for electric actuators should be discussed with the manufacturer Protective enclosure Protective enclosure of actuators MODACT MOK IP 67 according to SN EN 60529 Noise Level of acoust...

Страница 6: ...itter 1 x 100 Technical parameters Position scanning resistance Turning angle 0 320 Non linearity 1 Transition resistance max 1 4 Permitted voltage 50 V DC Maximum current 100 mA b Type CPT 1Az passiv...

Страница 7: ...internal wiring The internal wiring diagrams of the MODACT MOK actuators with terminal designation are shown in this Mounting and operating instructions Each actuator is provided with its internal wir...

Страница 8: ...are marked according to SN IEC 417 34 5550 If actuator is not provided with over current protection when purchased such protection must be provided externally 7 TECHNICAL DESCRIPTION The MODACT MOK M...

Страница 9: ...side of the actuator along with the external protective terminal When viewing the stop screws the right hand stop screw is designedfor the CLOSED position whereas the left hand stop screw is designed...

Страница 10: ...ometer is automatically preset The automatic adjustment of the potentiometer is usually provided already when the stop screws or the position limit switches are adjusted Current position transmitter C...

Страница 11: ...on of the current 20 mA was considerable repeat adjustment for 4 mA and 20 mA once again Disconnect the milli ammeter The screw secured by a drop of varnish situated nearer to the centre must not be t...

Страница 12: ...mit switches have been adjusted to the specified torque at the factory If they are required to be readjusted to another torque release the corresponding cam by means of the cam releasing screws whose...

Страница 13: ...oltage Speed of rotation of the actuator output shaft is given by the actuator type and variant it cannot be influenced by the regulator Connection of actuator with regulator and three phase electric...

Страница 14: ...s and connectors J1 signal terminal board J2 power terminal board 1 test input of logic control signal test A OPEN power output Open 2 GND control signal negative pole B CLOSE power output Close 3 IN...

Страница 15: ...mit switch means a position switch or moment switch of actuator connected so that it can stop the actuator motion in given direction During the auto calibration the regulator ZP2 measures the reaction...

Страница 16: ...e latest value of the parameter in the particular menu is selected another pressing of the push button SW2 will bring you back again to the first value of this parameter In this way you can select val...

Страница 17: ...n case of a change in setting the limit switches of the actuator or a change in mechanical properties of the valve e g if the gland is tightened Menu 6 Auto calibration error messages D 3 yellow D 4 r...

Страница 18: ...utput shaft rotates in the correct direction For this check depress the lever of the corresponding position limit or torque limit microswitch depending on the control mode while the actuator operates...

Страница 19: ...e faulty parts and adjusting the electromagnetic brake of the electric motor using this brake The brake should be readjusted after 0 5 x 105 switching operations the air gap between the armature and t...

Страница 20: ...x 230 0 90 45 MOK 63 MOK 125 MOK 250 MOK 500 MOK 1000 52 325 52 326 52 327 52 328 52 329 FCJ2B52D FCT2B54D FT2B52D FCJ2B52D FCJ4C52N FCT4C54N FT4C52NA EAMR56N04A FCJ4C52N FCT4C54N FT4C52NA EAMR56N04A...

Страница 21: ...ositioned at a 45 basic basic positioned at a 45 positioned at a 45 basic positioned at a 45 basic positioned at a 45 basic positioned at a 45 basic basic positioned at a 45 positioned at a 45 basic p...

Страница 22: ...4 16 16 19 19 0 1 2 3 4 5 6 7 8 9 W 0 1 2 3 4 5 6 7 8 9 W collar exchangeable inserts lever not available exchangeable inserts lever basic basic positioned at a 45 positioned at a 45 basic ppositioned...

Страница 23: ...23 Lever adapter with Type No 52325 actuator 386 367 301 P P pohled na z kladn desku M2 1 61 49 26 120 3 x 1 1 5 view of the base plate...

Страница 24: ...24 Lever adapter with Type No 52326 actuator 376 418 388 20 140 90 70 3 x 1 4 P P pohled na z kladn desku M2 1 Note Other dimensions are listed in the dimension table view of the base plate...

Страница 25: ...347 252 290 200 111 263 73 128 F 10 F 07 MOK 500 250 290 386 398 325 362 250 128 73 F 12 F 10 MOK 1000 250 290 386 398 325 362 250 128 323 73 155 F 12 Note Connecting of actuators with connector on s...

Страница 26: ...15 1 11 14 1 16 1 12 16 1 19 1 14 18 1 22 1 16 21 2 23 1 17 22 2 26 1 19 25 2 30 1 22 28 2 33 1 24 32 2 37 1 27 36 2 37 1 27 36 2 44 1 32 42 2 A Square end joint in the basic posistion B Square end j...

Страница 27: ...DCPT ZP2 RE Microcomputer position regulator KO Directional relay for the OPEN direction KZ Directional relay for the CLOSE position F Thermal safety F Thermal relay R1 R2 2x resistance protection 10...

Страница 28: ...ctuators with a one phase motor with the current transmitter without built in power supply or without transmitter with local control or without local control with the current transmitter with built in...

Страница 29: ...er and built in power supply with local control or without local control with the resistance transmitter without local control or with local control P 0872 E P0762V1 P 0834 Control phase Control phase...

Страница 30: ...5 1000 electric actuators with a one phase motor with the resistance transmitter and local control or without local control with the resistance transmitter and local control or without local control w...

Страница 31: ...th local control or without local control Wiring diagrams of MODACT MOK 125 1000 electric actuators with a one phase motor with the current transmitter without built in power supply or without transmi...

Страница 32: ...ocal control or without local control with the current transmitter without built in power supply or without transmitter with local control or without local control Wiring diagrams of MODACT MOK 125 10...

Страница 33: ...ol electric actuators with the one phase motor and position regulator P 0785 EZ MOK125 1000 1f motor Z2 N U2 17 5 4 9 7 6 8 13 11 12 10 16 15 14 23 20 18 19 22 21 27 25 26 24 28 R2 R1 C M 1 N L1 PE PO...

Страница 34: ...variant bez BMO 80 SA1 M D SA2 OTV ZAV L1 nap jen P0920 EZ N V W RZ RO U2 W2 V2 L2 L3 N PE 11 5 9 A B 10 7 6 B 9 10 11 5 A 3 3 7 6 Finder TEST d c sign l 0 4 20 mA 0 10 V Porucha max 24 V 2 W q 56 34...

Страница 35: ...a single point of one of the three circuits while other circuits should not be connected to the earth Analog signals should be transmitted via a screened conductor At the signal source the screening s...

Страница 36: ...ing between the control section cover and the power unit box for actuators Type Nos 52 325 Packing 224648301 Packing between the control section cover and the power unit box for actuators Type Nos 52...

Страница 37: ...NOTE...

Страница 38: ...NOTE...

Страница 39: ...turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT MOA OC E...

Страница 40: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Отзывы: