/ŶƐƚĂůůĂƟŽŶDĂŶƵĂů
^ǁŝƚĐŚ^tϭ
ĞƐĐƌŝƉƟŽŶ
DIP1
ON
The production equipment is water-operated.
OFF
The production equipment is Direct Expansion (DX) (default option).
DIP2
ON
The production equipment is Boiler.
OFF
DX indoor unit (Split or VRV) or Fancoil (by default).
DIP3
ON
Centralized system. The equipment only obeys the commands that reach it from the
RS485/ Rem bus.
OFF
system. The
obeys the last order that arrives, whether from the
RS485/ Rem bus or from the thermostats. No priority (default option).
DIP4
ON
Radio transmission frequency 433 MHz. Corresponds to Fr00 of the ZOE-RC thermostats
OFF
Radio transmission frequency 434 MHz. Corresponds to Fr00 of the ZOE-RC thermostats
(default option)
DIP5
ON
Slave VRV for Direct expansion installations (requires DIP 7 ON) / Water type 4T
installations .
OFF
Master VRV for Direct expansion installations / Water 2 T installations (by default).
DIP6
ON
Settings for Eu.Bac operation (should also be enabled in the thermostats).
OFF
Settings for standard operation (by default)
DIP7
ON
Not combined. There is a single production unit: air or water. For SLAVE VRV installations
(DIP 5 ON also required ).
OFF
Combined. Air and water production units are combined (by default).
DIP8
ON
Unit in work mode.
OFF
Unit in learning mode. To start up the installation.
ŚĞĐŬƚŚĞĚŝĂŐƌĂŵƐĨŽƌĞĂĐŚƚLJƉĞŽĨŝŶƐƚĂůůĂƟŽŶƚŽƐĞĞƚŚĞĐŽŵďŝŶĂƟŽŶŽĨƚŚĞĚŝīĞƌĞŶƚ/WƐ͘
&ŽƌƌĞŵŽƚĞĐŽŶŶĞĐƟŽŶƐǁŝƚŚD^͕ĐŽŵďŝŶĞĚŝŶƐƚĂůůĂƟŽŶƐďĞƚǁĞĞŶDĂƐƚĞƌͬ^ůĂǀĞďŽĂƌĚƐ͕ĂƐŬƚŚĞƚĞĐŚŶŝĐĂůĚĞƉĂƌƚŵĞŶƚ͘
ǁǁǁ͘njŽŶŝŶŐ͘ĞƐ
8 SW1 central ZITY advanced settings:
The SW1 switch is used to configure the
ZITY control unit according to the type of installation and operating frequency.
DIP 8 is used to place the unit in learning mode during start-up (see the corresponding
section).
ŝƌĞĐƚdžƉĂŶƐŝŽŶ
sZ&
^>s
&ĂŶŽŝůϮƚ
&ĂŶŽŝůϰƚ