4 Most common errors
4.1 For all installations:
ERROR
INDICATOR
CAUSE
SOLUTION
1
On supplying 230Vac to
the control unit, no LED
lights up on the control unit
No voltage or no
learning
·
Check that voltage is reaching the ZITY
control unit (230VAC ±10%).
·
Ensure the learning process has been
carried out.
2
5 minutes after switching
on the control unit, all zone
LEDs start to flash and all
grilles are closed
Incorrect settings
·
Check the settings of the thermostats.
Make sure that they are
to the con-
trol unit
.
·
Repeat the learning process.
·
In Radio systems, check whether it works at
a shorter distance and relocate the antenna.
·
In Radio systems, check the operating fre-
quency between thermostats and central are
the same.
3
Some of the zone LEDs do
not light up and the rest do
Learning error
·
The thermostat corresponding to the
LED switched off has not been recognised
in the learning process
.
·
Reprogram the thermostat and repeat the
learning process, making sure that all LEDs
light up during the process, waiting for 30s
before finishing.
4
Some of the zone LEDs are
flashing and the dampers of
these zones close
Poor
communication
·
The control settings have been changed
since the learning process. Configure it
again.
·
Check that the thermostat is in the installa-
tion.
·
Check the location and the batteries in
the thermostats via Radio.
·
Checking the wiring in the wired thermostats
5
The R7 LED in the relay row
flashes and the zone LEDs
light up in red
More than one
Master
·
There are two thermostats declared as
Master in the installation. Re-configure the
thermostats in conflict and leave only one
Master.
6
The control unit does not
show any error but the unit
does not start up
Time programming
·
Check that the thermostat PROG function
is not enabled and whether it corresponds
to a switch-off time or is not set correctly.
7
The grille closes when it has
to open (and vice versa)
Motors
incorrectly
connected
·
Check motor connection. Polarity (black -,
red +).
·
Check that ti is tested in the correct operat-
ing mode (Cool/ Heat).
8
One of the grilles is not
working
Zone regulator
connection
·
Check motor connection. Polarity (black -,
red +).
·
Check that the regulator is not obstructed.
9
All grilles are operating
correctly, but the climate-
control unit does not work
Climate-control
until incorrectly
connected
·
Check the control unit settings according to
the type of the equipment.
·
Check the connection of the equipment with
the board.