ZSI-330 User Manual
Issue 01
Page 19 of 30
Start timeout
The time, from the last time the monitor was switched, before the video detection sequence is started.
The timeout is overridden when a remote operator disconnects a call, in which case the sequence starts
immediately. Range
1 – 65535 minutes.
Default =
1 minute
Site controller pass through
This box disables internal event handling, instead passing all alarm triggers to a site controller.
Note this function is
not currently available.
Default =
Disabled
Alarm Contacts
Setup alarm detection on the 16 contact inputs.
For each of the 16 contact inputs, the following can be configured:
Trigger state
The input state that triggers an alarm. Options:
Open, Closed, Disabled
Z
S
I
-
3
3
0
Default =
Closed
Trigger time
The minimum time the input state must match the trigger state, before an alarm is raised. Range
0 – 255 (
x
10ms)
Default = 5 (
x
10ms)