15 

 

Led lit continuously  Meaning 

“défaut thermique 

ventilateur” 

= fan heat fault 

Not used on Sirocco 

“défaut pressostat 

HP ou BP” 

= high or low 

pressure switch fault 

 triggering HP and/or LP switch and/or phase order relay KA4 (only on 
Sirocco three-phase) 

- HP : check that the ventilator is operational, that the air filter is clean and 
the belt is tight enough,  
-  LP: insufficient gas, call a specialist,  
-  KA4: check for the presence of the 3 phases, if so, see §1.4.2. 

“défaut thermique 

compresseur” 

= compressor heat 

fault 

Not used on Sirocco 

“déclenchement 

alarme” 

= Triggering of the 

alarm 

- HP and/or LP switch triggered more than 3 times in one hour  
- order phase relay KA4 triggered (only on Sirocco three-phase) 

“défaut hors 

température” 

= temperature range 

fault 

-

  temperature < than 10°C or > than 40°C (compressor stopped),  

-

  restart sensor is out of order.  

-

  In all cases, if the ventilator is active before the triggering of this fault, it is 

maintained for 3 minutes before stopping. 

-

  If the returns to within its operating range:  

-

  there is a 30 seconds delay before the fault is cleared, 

-

  there is a 3 minute delay before restarting the compressor and the fan (if a 

dehumidification request is still active) 

“cycle de dégivrage” 

= defrosting cycle 

-

  cooling circuit temperature < than -5°C or > than 40°C,  

-

  a defrosting cycle is in progress (temperature is >-5°C). The compressor is 

stopped and ventilation is maintained, 

-

  the defrosting sensor is out of order. 

The defrosting cycle stops when the temperature of the sensor goes over 
2.2°C. If the sensor is out of range (<-5°C or >40°C) during the active 
defrosting cycle, this LED remains on for 3 minutes with the ventilation 
operating, before it stops.  
In all cases, if the ventilator is active before the triggering of this fault, 
ventilation is maintained for 3 minutes before stopping. 
If the sensor returns within its operating range:  

-

 there is a delay of 30 seconds before the fault is cleared, 

-

 there is a 3 minute delay before the compressor and fan restart (if a 

dehumidification request is still active) 

 
 

Others 

Description 

 

“VI/VP switch”

 

“intermittent ventilation” (standard setting)  
or “permanent ventilation” (to permanently circulate the pool hall air) 
Using VI, a post-ventilation is active for 3 minutes.  
The ventilation is active when:  

-  dehumidification is triggered,  
-  a defrosting cycle is started, 
-  pool hall air heating is triggered, 

active for at least 5 minutes in one hour without any of these 

triggers.

 

On VP, the compressor starts after a delay of 3 minutes. 

“Connecteur module 

de prog.”  

= programming 

module connector 

 

 

ECP 600 programming connector or implementation of a diagnosis module 
by the technical support department

 

 

ECP 600 250Vac T=10A 6,3x32 fuse 

 
 
 

Содержание SIROCCO 110

Страница 1: ...Installation instructions Air dehumidifier for indoor swimming pools R f N D 005 A EN Ver 02 2010 SIROCCO 55 80 110...

Страница 2: ...to surrounding air 6 1 3 5 Inset connection 7 1 3 6 Connection of the condensation drainage 8 1 3 7 Electric connections 8 1 3 8 Connection of the options 12 1 4 Commissioning 13 1 4 1 Starting the a...

Страница 3: ...on studs x4 dowel x 2 long bolt x 2 For Sirocco can be inset sleeve x 2 frame with cadre suction grid and filter x 1 frame with blowing grid frame fixture kit x 1 The appliance must be transported upr...

Страница 4: ...0 unit protection class Sirocco ambient IP 44 Sirocco can be inset IP 45 class I refrigerant gas R407C refrigerant charge see product information plate 1 2 2 Operating conditions operating range 10 C...

Страница 5: ...installed outside volumes 0 1 and 2 the appliance has a protection index of at least IP X5 In volume 2 see figures 702A and 702B the appliances must be either class II for lighting or class I protecte...

Страница 6: ...hat the materials used are compatible with a swimming pool environment the walls are sufficiently waterproofed and insulated to avoid condensation forming in the room when relative humidity reaches 60...

Страница 7: ...with two bolt screws washers and plugs supplied in a solid wall Pool minimum distance Sirocco 55 80 110 suction grid blowing grid Hygro Control condensation drainage air renewal system see 1 3 2 fres...

Страница 8: ...leeves and mark the two inside anchoring points install the fixing plugs into the solid wall using the marks present the appliance again and from the inside screw in the bolt screws washers into each...

Страница 9: ...7 3 Cable sizes Supply cable size for cables of a maximum length of 20 metres calculation basis 5A mm this must be checked and adapted depending on installation conditions Option Voltage Nominal powe...

Страница 10: ...echnician must install the device cables If the power cable is damaged it must be replaced by a qualified technician or by a Zodiac Pool Care Europe service station Main supply see 1 3 7 3 Regulation...

Страница 11: ...desired relative humidity Display of the ambient temperature and or humidity by pressing once C and or RH blink To exit press or wait 10 seconds only if your appliance is fitted with the hot water ba...

Страница 12: ...ll the digits light or and the appliance starts up Parameter setting in hygro thermostat or hygrostat mode Hygro Control must be on standby press and for 3 seconds hygro thermostat mode press or to se...

Страница 13: ...nput to the hot water battery 45 C minimum 90 C maximum Maximum pressure water battery circuit 3 bars Power returned to the air at 27 C input to the hot water battery Connection to the primary circuit...

Страница 14: ...s a heating request is active This safety device has two levels of triggering 1 by THS safety thermostat if the T C is 65 C it is automatically reset 2 if the temperature continues to increase the sec...

Страница 15: ...e thermostat function request active if 6Vac 50Hz between 2 and 4 8 input 12Vac 50Hz fan heat fault shunted not active fault active if 0Vac 50Hz between 8 and 4 d faut thermique ventilateur led lit up...

Страница 16: ...emperature than 5 C or than 40 C a defrosting cycle is in progress temperature is 5 C The compressor is stopped and ventilation is maintained the defrosting sensor is out of order The defrosting cycle...

Страница 17: ...ol and make a shunt between terminals 1 5 7 and check the voltage between 4 5 12V Replace the ECP 600 no yes Replace the Hygro Control See faults table 2 1 The appliance does not work No fault display...

Страница 18: ...o Is the appliance being ventilated all the time Voltage on the compressor terminals 230V or 400V yes Replace the contactor no no Re connect the Hygro Control and check that it is operational Wait for...

Страница 19: ...teries evaporator condenser and hot water by removing the cover from the appliance switched off Depending on the condition clean with a silk brush and a vacuum cleaner 3 2 Spare parts Naming Item numb...

Страница 20: ...e back to the reseller or ask the transporter to take it back This is known as a One for One exchange Otherwise please take it to a waste collection centre if your local council has set up a selective...

Страница 21: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 22: ...1 Electric diagram Sirocco 55 80 110 single phase...

Страница 23: ...2 Sirocco 110 three phase...

Страница 24: ...y 230Vac 50Hz for battery circulator or used for electric logic of the heating option by electric backing E1 high pressure switch E2 low pressure switch OAE back up heating option R heating resistor T...

Страница 25: ...4 Dimensions weight without option A B C Kg mm Sirocco 55 65 1030 620 653 Sirocco 80 75 1220 810 843 Sirocco 110 85 1410 1000 1033...

Страница 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 28: ...Care Europe Boulevard de la Romanerie BP 90023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Global provider of innovative pool products and services Produits et services innova...

Отзывы: