background image

Page 7

3. 

Secure the backplate to the box using the screws 
that came with the electrical box.

4. 

Drill out a ½" hole and insert the round seal 
supplied with the kit. A remote cable will run 
through the middle hole of the backplate and 
into the electrical box.

Figure 2.  Controller Components

2.5 

Installation of the Backplate on a Flat 
Wall

   CAUTION

Do not expose the user interface to direct sunlight. Too 
much direct sunlight will darken the LCD screen, and it 
will no longer be readable.

1. 

Turn off the pump at the control panel.

2. 

Turn off all electrical power to the pump at 
the main junction box or at the circuit breaker 
providing electrical power to the pump.

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the ePump™ 
electrical circuit before starting the procedure. Failure to 
comply may cause a shock hazard resulting in severe 
personal injury or death.

3. 

A minimum of two (2) fasteners (installer 
supplied) are required when installing to a flat 
wall to hold the controller securely.

4. 

The backplate has ten (10) mounting holes to 
choose from. Only drill out the backplate holes 
that will be used. See Figure 2.

5. 

Mark the hole locations on the wall and use the 
fastener to secure the backplate to the wall.

6. 

At the bottom of the backplate, cut the two 
(2) tabs out with an appropriate tool, such as a 
Stanley knife, and route the cable through the 
open channel.

2.6 

Connection to the Jandy ePump™ 
Variable Speed Pump

The following steps provide the procedure for 

installing the controller to a Zodiac ePump™ variable 
speed pump.

1. 

Turn off all switches and the main breaker that 
supplies power to the pump.

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the ePump™ 
electrical circuit before starting the procedure. Failure to 
comply may cause a shock hazard resulting in severe 
personal injury or death.

2. 

Attach the four (4) wires in the RS-485 cable 
to the RS-485 connector. Make sure the colors 
match the positions on the User Interface. See 
Figure 3.

3. 

Turn on all switches and the main breaker 
feeding power to the pump.

4. 

Verify the operation of the controller. If the 
controller displays 

FAULT PUMP NOT 

CONNECTED

, re-check the wiring and the 

DIP switch address setting on the pump.

Figure 3.  Wiring the User Interface to the Zodiac 

ePump™

  

Variable Speed Pump

2.7 

Zodiac ePump™ Variable Speed 
Pump Switch Settings

For the ePump™, the 4-position dip switch is 

located at the rear of the pump, as shown in Figure 3.

Содержание ePump

Страница 1: ...t must be installed and serviced by a professional pool spa service technician The procedures in this manual must be followed exactly Failure to follow warning notices and instructions may result in p...

Страница 2: ......

Страница 3: ...r 9 3 1 The ePump Controller 9 3 2 The ePump Controller Interface 9 3 3 Basic Functions 10 Section 4 User Operation 10 4 1 OFF Mode 10 4 2 RUN Mode 10 4 3 Manual Start and Stop 10 4 4 Pump Speed Setti...

Страница 4: ...en or missing Never replace a suction fitting with one rated less than the flow rate marked on the equipment assembly WARNING To Reduce the Risk of Injury a The water in a spa should never exceed 40 C...

Страница 5: ...mometer Do not use a spa or hot tub immediately following strenuous exercise Prolonged immersion in a spa or hot tub may be injurious to your health Do not permit any electric appliance such as a ligh...

Страница 6: ...r Components The ePump controller assembly See Figure 2 contains the following components 1 ePump Controller 2 Mounting Gasket 3 Backplate 4 Round Seal 5 Six 6 Screws Additional materials are required...

Страница 7: ...igure 2 5 Mark the hole locations on the wall and use the fastener to secure the backplate to the wall 6 At the bottom of the backplate cut the two 2 tabs out with an appropriate tool such as a Stanle...

Страница 8: ...n on all switches and the main breaker feeding power to the ePump 5 Verify the operation of the contact closures If the correct speed is activated when the closure is activated the ePump starts and th...

Страница 9: ...in breaker feeding power to the ePump 8 If the installation is working properly the fireman s switch will open 20 minutes before the booster pump shuts down the ePump will continue to run for 30 minut...

Страница 10: ...time of day clock 4 2 RUN Mode When the pump is running not off the controller displays n label 00 00 RPM xxxx where n label is the number and label of the selected preset 00 00 is the time of day clo...

Страница 11: ...e only within a certain range The minimum and maximum limits of the range are set by the installer 4 5 Timeclock Setup and Operation The controller allows the user to create timed pump programs on pum...

Страница 12: ...hen starting the pump via a timed program the pump will first run at the priming speed for the priming duration as set by the installer If a program overlap occurs the pump will immediately start at t...

Страница 13: ...ller for further information 4 7 Pump Freeze Protect To help protect against pump damage the controller monitors the temperature inside the pump If enabled pump freeze protect will start the pump at t...

Страница 14: ...Minimum and maximum pump speeds eStar speed Pump Freeze Protect operation 5 1 Entering Service Setup NOTE The ePump controller must be in the OFF mode all LED s lights must be off before entering the...

Страница 15: ...To clear the fault history press either arrow key 5 5 Priming Speed and Duration The ePump controller will command the ePump to operate at the priming speed for the priming duration specified except d...

Страница 16: ...protect equipment and plumbing for short periods of freezing only It does this by activating the filtration pump and circulating the water to prevent freeze inside equipment or plumbing Freeze protec...

Страница 17: ...SET Press the MENU button to display the currently selected preset Using the arrow keys choose the preset to be changed Press MENU to select The controller displays SELECT LABEL TYPE Select GENERAL or...

Страница 18: ...election From the setup menu select LANGUAGE using the arrow keys Press MENU Using the arrow keys select the desired language Press MENU to save the selection 6 7 Run Duration Presets 3 and 4 Only Pre...

Страница 19: ...Page 19 Section 7 Menu Flow Chart...

Страница 20: ...H0352000 Zodiac Group Australia Pty Ltd 219 Woodpark Road Smithfield NSW 2164 Ph 1800 688 552 Fax 02 9756 3987...

Отзывы: