ZMC408CE Motion Controller Hardware Manual V1.5
→
Terminal Definition
Terminal
Name
Type
Function
DA0
Output
Analog output terminal: AOUT(0)
DA1
Analog output terminal: AOUT(1)
AGND
Public End
Unique public end of this analog
AD0
Input
Analog input terminal: AIN(0)
AD1
Analog input terminal: AIN(1)
3.4.1.
AD/DA Analog Input/Output Specification & Wiring
→
Specification
Item
AD
(
0-1
)
DA
(
0-1
)
Resolution
12-bit
12-bit
Data range
0-4095
0-4095
Signal range
0-10V input
0-10V output
Data refresh ratio
1KHz
1KHz
Voltage input impedance
/ output load
>40K
Ω
(voltage input
impedance)
>1KΩ
(voltage output
load)
→
Wiring Reference
→
Wiring Note:
⚫
The analog input/output wiring method is as shown in the figure above, and the
external load signal range must match with this signal range.