CANFDNET-400U
High-performance Four-channel CANFD Bus-to-Ethernet Converter User Manual
©2021 Guangzhou ZLG Microelectronics Technology Corp.,Ltd.
13
User Manual
synchronization jump width. The clock is fixed at 60 MHz;
3. After setting, click the calculation button at
③
to list the calculation results of the
corresponding baud rate parameters;
4. Select the arbitration domain baud rate for the appropriate sampling point. If the
value is selected, the blue background color appears, indicating that the value is
selected, as shown in
④
;
5. Select the data domain baud rate for the appropriate sampling point. If the value
is selected, the blue background color appears, indicating that the value is
selected, as shown in
⑤
;
6. Click the copy button at
⑥
to copy the value of the custom baud rate. Paste this
value into the custom baud rate text box.
Figure 3.5 Steps for using the baud rate calculator