Chapter 2: Installation
18
ZP1-X3 Installation Manual
Connecting the batteries
The control panel requires two 12 V, 7.2 or 12 Ah rechargeable, sealed, lead-
acid batteries.
Batteries must be installed in series, at the base of the control panel cabinet. Use
the battery lead and bridge provided and connect batteries to the BATT
connector on the control panel PCB, as shown below. Polarity must be observed.
Note:
If the control panel indicates a Supply Fault, then the batteries may need
to be replaced. See “Battery maintenance” on page 57.
Figure 10: Connecting the batteries
Caution:
Risk of equipment damage. No other equipment may be connected to
the BATT connector.
Connecting other equipment
Connecting auxiliary equipment
Connect auxiliary equipment to the 24VAUX output as shown in Figure 11 on
page 19. The 24 VDC auxiliary output is supervised for short circuit and voltage
output.