Chapter 3: Configuration and commissioning
ZP1-X3 Installation Manual
53
Figure 16: Battery startup button
Functional tests
Create a short circuit and an open circuit in each zone to test fault reporting for
both types of fault.
If available, activate a fire manual call point to test manual fire alarm reporting.
The control panel should override any configured delays and activate alarm
notification devices and fire routing (where applicable) immediately.
Activate a fire detector to test automatic alarm reporting. The control panel
should initiate any configured delays and activate alarm notification devices and
fire routing (where applicable) once the delay time has elapsed.
Verify the extinguishing functionality without connecting the extinguishing agent
to the actuator. Test these functions:
• Manual (MCP Start) and automatic (extinguishing zone detectors)
extinguishing activation
• Emergency override manual call points (MCP Hold and MCP Abort)
• Extinguishing activation sounders
• Remote manual-only control and safety door monitoring (if available)
• Delay to actuator activation
• Extinguishing released sounders and optical warning panels or signs are
activated by the extinguishing agent flow signal (if configured)
Using a multimeter, verify that the fault relay is activated when a fault is reported
and that the fire alarm relay is activated when a fire alarm is reported.
Содержание ZP1-X3
Страница 1: ...ZP1 X3 Installation Manual P N 501 419203 1 10 REV 00 12 ISS 27JUN11...
Страница 6: ...iv ZP1 X3 Installation Manual...
Страница 26: ...Chapter 2 Installation 20 ZP1 X3 Installation Manual...
Страница 64: ...Chapter 4 Maintenance 58 ZP1 X3 Installation Manual...
Страница 71: ...Chapter 5 Technical specifications ZP1 X3 Installation Manual 65 Figure 17 Control panel cabinet without cover...
Страница 72: ...Chapter 5 Technical specifications 66 ZP1 X3 Installation Manual Figure 18 Control panel cabinet with cover...
Страница 82: ...Appendix B Regulatory information 76 ZP1 X3 Installation Manual...
Страница 86: ...Index 80 ZP1 X3 Installation Manual...
Страница 87: ......
Страница 88: ......