Chapter 3: Configuration and commissioning
ZP1-X3 Installation Manual
37
Display Description
Safety door monitoring is used (on).
Safety door monitoring is not used (off).
Safety door fault delay
Use this menu to configure a delay from 10 to 90 seconds (in steps of 5 seconds)
in reporting safety door faults caused by incorrect status (open or closed). The
default setting is 30 seconds.
To configure a safety door delay:
1. Set the display as shown below, and then press Enter.
The Door Fault/Disabled LED flashes fast to indicate that the delay
configuration menu is active.
2. Select a delay value from 10 to 90 seconds using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Pressure switch type
Use this menu to configure the low pressure switch for detection of the container
pressure. Correct pressure can be either normally closed (NC) or normally open
(NO). The default setting is normally closed (NC).
To configure the pressure switch type:
1. Set the display as shown below, and then press Enter.
The Low Pressure LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Содержание ZP1-X3
Страница 1: ...ZP1 X3 Installation Manual P N 501 419203 1 10 REV 00 12 ISS 27JUN11...
Страница 6: ...iv ZP1 X3 Installation Manual...
Страница 26: ...Chapter 2 Installation 20 ZP1 X3 Installation Manual...
Страница 64: ...Chapter 4 Maintenance 58 ZP1 X3 Installation Manual...
Страница 71: ...Chapter 5 Technical specifications ZP1 X3 Installation Manual 65 Figure 17 Control panel cabinet without cover...
Страница 72: ...Chapter 5 Technical specifications 66 ZP1 X3 Installation Manual Figure 18 Control panel cabinet with cover...
Страница 82: ...Appendix B Regulatory information 76 ZP1 X3 Installation Manual...
Страница 86: ...Index 80 ZP1 X3 Installation Manual...
Страница 87: ......
Страница 88: ......