Chapter 3: Configuration and commissioning
ZP1-X3 Installation Manual
45
Zone configuration
Use this menu to configure zone settings for each zone in your fire alarm system.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The red Zone LED flashes fast to indicate that the corresponding zone
configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display Description
Passive end-of-line
Active end-of-line
Passive end-of-line with CleanMe [1]
Active end-of-line with CleanMe [1]
[1] The CleanMe feature is not available for Ziton devices.
Zone delay
Use this menu to configure zone delays, on or off, for each zone in your fire
alarm system. The default setting is ON.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
Содержание ZP1-X3
Страница 1: ...ZP1 X3 Installation Manual P N 501 419203 1 10 REV 00 12 ISS 27JUN11...
Страница 6: ...iv ZP1 X3 Installation Manual...
Страница 26: ...Chapter 2 Installation 20 ZP1 X3 Installation Manual...
Страница 64: ...Chapter 4 Maintenance 58 ZP1 X3 Installation Manual...
Страница 71: ...Chapter 5 Technical specifications ZP1 X3 Installation Manual 65 Figure 17 Control panel cabinet without cover...
Страница 72: ...Chapter 5 Technical specifications 66 ZP1 X3 Installation Manual Figure 18 Control panel cabinet with cover...
Страница 82: ...Appendix B Regulatory information 76 ZP1 X3 Installation Manual...
Страница 86: ...Index 80 ZP1 X3 Installation Manual...
Страница 87: ......
Страница 88: ......