SR981S/SR982S operation manual of solar pump station
Page 29 of 85
System 10: 1 tank + T-valve controlled by return heating
Description:
Controller compares the temperature between T1 of collector array and T2 of tank, when
temperature difference reaches its switch-on value (DT1O), then P1 is triggered, tank is
heated until tank temperature reaches its maximum value or when temperature difference
(DT1F) drops to the switch-off value, then P1 is ceased.
Another temperature difference between T4 and T6 (DT2O/DT2F) to control T-valve R1 to
heat the heating return by solar.
Note:
when T4 is not installed, then temperature difference between T3, T6 ( DT2O/DT2F)
is used to control T-valve R1
When T3, T4 are not installed, then temperature difference between T2, T6 ( DT2O/DT2F)
is used to control T-valve R1
See detailed in 8.4.8/8.4.9
Input ports
Description
Output ports
Description
T1
Sensor of collector array
T2
Sensor on the bottom part of tank
P1
Pump 1 for collector array
T3
Sensor on the top part of tank
H1
Back-up heat resource
T4
Sensor on the middle part of tank
T6
Sensor on the heating return pipe
R1
T-valve for heat the heating
return
T7
Sensor on the return pipe
T8
Sensor on the flow pipe( SR981S no)
List of available auxiliary functions in this system (functions are selectable)
Input ports
Description
Output ports
Description
T5
Sensor on solid fuel boiler
R2
Pump for solid fuel boiler (See
Paragraph 8.5.2)