– Parameters  

  

This register is used to set up the Maximum motor current, the reaction speed of the motor and 

Move Distance speed setting.  
  

Register 

 

Name 

 

Byte Data  

 

Default 

 

0x01 

 

Parameters  

 

Data 0 = NA 

 

Data 1 = Max Current 

 

Data 2 = Reaction  

 

Data 3 = Move Distance Speed MSB 

 

Data 4 = Move Distance Speed LSB 

 

0x00 

 

0x0F 

 

0x46 

 

0x00 

 

0x00 

 

  
  

When the Max Current is measured in the motor phase windings, the PWM supplied to the 

windings will be reduced to prevent an over current failure in the motor, application or 
controller.  
  

The reaction speed is only used when the PID is NOT enabled. The reaction speed varies the 

acceleration and deceleration rate of the motor. Smaller values result in a much more responsive 
motor, and higher values result in a more laid-back motor.  
  

The move distance speed refers to the maximum speed the motor will accelerate up to while 

performing a Move Distance command (0x03).  
  

 

 

Содержание ZDBL50DCUART Series

Страница 1: ...s is a trading name of Round Bank Engineering Ltd Unit 4B Top Land Business Park Hebden Bridge West Yorkshire HX7 5RW enquiries Zikodrive com www Zikodrive com 44 0 1422 647177 Zikodrive ZDBL50DCUART...

Страница 2: ...tents Introduction 3 Overview 3 Specifications 3 Setting Up 4 Programming Manual 6 The UART Protocol 6 Protocol Setup 6 Recommended Software 6 The Zikodrive Protocol 7 CheckSum formula 7 Shortlist of...

Страница 3: ...ations Up to 28Vdc Up to 50Adc Sensored BLDC trapezoidal Block commutation control Four Optically Isolated Inputs Two Power Outputs 24V up to 2A Modular design connects to many Break Out Boards that c...

Страница 4: ...em wired up incorrectly as the motor will not turn may be possibility of damage to either the motor and or controller possibly even PSU due to high currents Power Wires 12 28Vdc must be applied to the...

Страница 5: ...TX transmitting from the Master controller must be connected to the RX receiving pin on the ZDBL50DC controller The TX transmitting from the ZD SERIES UART must be connected to the RX receiving of the...

Страница 6: ...rd and derived by the Zikodrive engineers to provide fast and efficient data transfer The Data is transmitted and received in 10 packets of 8bit binary Bytes Protocol Setup BAUD RATE 19200 START BITS...

Страница 7: ...rocess the given command If the command was rejected all data will be disregarded with a NACK 0x15 and error code and a new command must be sent Example 1 Basic Command From Master 0x7A 0x64 0x01 0x02...

Страница 8: ...SB Data 4 Speed LSB 0x00 0x00 0x00 0x00 0x00 0x01 Parameters Data 0 NA Data 1 Max Current Data 2 Reaction Data 3 Move Distance Speed MSB Data 4 Move Distance Speed LSB 0x00 0x0F 0x46 0x00 0x00 0x02 Mo...

Страница 9: ...der and motor windings However if Byte 0 is equal to 0 the direction will be A and if Byte 0 is equal to 1 the direction will be B Data Bytes 1 2 are not required and will not be read The speed refers...

Страница 10: ...5RW enquiries Zikodrive com www Zikodrive com 44 0 1422 647177 As 925 is half the max 1850 the motor will move in direction B at half the PWM duty cycle This varies depending on what motor is used If...

Страница 11: ...a 3 Move Distance Speed MSB Data 4 Move Distance Speed LSB 0x00 0x0F 0x46 0x00 0x00 When the Max Current is measured in the motor phase windings the PWM supplied to the windings will be reduced to pre...

Страница 12: ...n be changed by Zikodrive the output is scaled to count every 6 motor commutation point as a single unit of distance So for a 5 pole motor you will get 30 commutation points per revolution 5 3 hall se...

Страница 13: ...sets the power bridge configuration into one of two different modes Normal running conditions will resume when the appropriate UART command is received Register Name Byte Data Default 0x04 Motor Mode...

Страница 14: ...le Data 1 Commutation Points Data 2 Proportional Value Data 3 Integral Value Data 4 Derivative Value 0x01 0x0F 0x64 0x00 0x00 0x06 Revert to PWM Analogue Data 0 4 NA NA Internally the micro controller...

Отзывы: