Operating Instructions Z-D-15/35/55E-..
Enclosure
__________________________________________________________
_________________________________________________________________________________
L-BAL-E321-GB 2021/11 Index 002
41/44
9.1.1
Technical Data Active harmonic filter Z-D-15E-..
Electrical data
Network type
3 phase with/ without neutral 3P4W/3P3W
Rated voltage
380-480 V (+10 % / -15 %)
Rated current
15 A
Mains frequency
50 Hz / 60 Hz (
5 Hz)
Harmonic compensation
1.-60. Harmonic
Response time
20 µs
Full response time
5 ms
Filter performance
>96 %
Switching frequency
40 kHz-60 kHz, typical 50 kHz
Technology
Advanced SIC
System topology
Two Level Topology
Function
Harmonic compensation, power factor correction, three phase
balancing
Efficiency
η
>99,4% at nominal load
Power losses
207 W at 30 kW nominal power
User-Interface & Remote monitoring
HMI
Not present / extern
Communication protocol
RS485
PC-Software
V3.2.3
Installation / Configuration
Noise
<60db
Current transformer ratio
30/5~60/5
Cooling
Forced air cooling
Air flow requirement
>105m³/h
Mounting
Wall mount
Parallel configuration
Unlimited
Extensions
Modules in parallel
Protection level
IP20
Cable entering
bottom
EMC regarding IEC60038
class A (EN61000-6-4*, EN 61000-6-1)
Environmental
Ambient temperature
-10
℃
~40
℃
Temperature-Derating
Derating above 40
℃
(3%/K)
Maximum temperature
50
℃
Permissible temperature range for transport
-25 °C~+70 °C (regarding EN 50178)
Permissible temperature range for storage
-25 °C~+55 °C (regarding EN 50178)
Relative Humidity
5%~95% Class F without condensation
Altitude
below 1000m
Altitude Derating
above 1000m (5%/1000m to 4000m)
Weight, Dimensions, Certifications
Weight
10 kg
Dimensions W*D*H[mm]
89*417*260
Certifications
CE
*Warning note:
This device is not intended to be used in residential areas and cannot ensure adequate
protection of radio reception in such environments.