PIN 9095
Restore factory setting = delivery status
Setpoint
Setpoint
setting range: 0.0..40.0
°
C
Factory setting: 20.0
°
C
Stall on
Cot
ON
: compartment control switchedon
OFF
: compartment control switchedoff, no fault indications
Stall Pre-heat
: The automatic ventilation regulation andthe temperature monitoring
are switchedoff. The stall is pre-heateduntil the value set in the Installation menu
under
“
Diverse
” “
Pre-heat Nominal
”
is reached(stall heater H1).
Stall Wash
: The automatic ventilation regulation andthe temperature monitoring are
switchedoff. Constant ventilation with the set value
“
Wash Air
”
(factory setting 50 %).
The heater 1 operates at the set value for
“
Wash Temp.
”
(
“
Diverse
”
).
Freshairtemp.
Freshairtemp.
Display of the measuredsupply air temperature with which the device operates.
Depending on the operating mode (master or slave) the value comes from the sensor
to input
“
E2
”
or via bus from the master.
If in the Installation menu under IO Setup the
“
Supply air temp.
”
is switchedto
“
OFF
”
or
if no outside temperature is transmitted when programming on bus, the device operates
with a
xedvalue of 15.0
°
C ! If no sensor is connectedwhen programming to
“
E2
”
the
fault message
“
ALARM sensor E2 is output.
”
E2
E2
Display of actual value at
“
E2
”
.
For temperature sensor display in
“°
C
”
, if no sensor is connecteddisplay 81.6
°
C.
For humidity sensor display in in
“
% R.H.
”
E3
E3
Display of actual value at
“
E3
”
.
As long as input in
“
IO Setup
”
not activateddisplay:
|
- - - - -
|
When temperature sensor activated
“
TF..
”
in IO Setup:
“
D1 Function
”
=
|
6D
|
.
Display in
°
C, if no sensor is connecteddisplay 81.6
°
C.
Max. load
Max. load
Display for peak loadfan.
If a variant fort he peak loadfan is programmedin the
“
Installation
” – “
Ventilation
”
menu, the operating state (ON / OFF) or the control 0..100% is displayed here.
As long as no
“
Peak loadvariant
”
programmeddisplay:
|
- - - - -
|
Temp. Min. Value
Temp. Min. Value
The lowest temperature in the compartment (at input
“
E1
”
) since device reset (mains
supply ON / OFF) or a manual reset with
“
Reset Min-Max
”
Temp. Max. Value
Temp. Max. Value
Maximum temperature in the compartment (at input
“
E1
”
) since device reset (mains
supply ON / OFF) or a manual reset with
“
Reset Min-Max
”
Reset Min-Max
Reset Min-Max
Reset of minimum andmaximum values. I.e., the temperature measurement starts
again.
Exhaust air sum
Exhaust air sum
Exhaust air total of the whole ventilation system.
If several devices are connected via a bus the momentarily conveyed exhaust air
volume of every stall is measured and added under consideration of the exhaust air
percentage (menu Ventilation
–
Exhaust air percentage). The total of the devices
involvedin the ventilation system may not exceed100 %. A fault message
“
Exhaust air
total
”
is output at a total above 100 %.
Language
Language
Menu language by the factory set to
|
German
|
.
In this menu different national languages can be selected (GB = English, D = German
...).
Operating Instructions
UNIcon / Acontrol
Settings for operation
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
48/83