7.13.5
Set protection = PIN Lock
PIN Lock
PIN Lock
The
“
PIN Lock
”
is set =
|
OFF
|
at the factory, i.e. all settings are possible without
entering the PIN.
With
“
PIN Lock
”
=
|
ON
|
settings are only possible when the PIN
|
0010
|
has been
enteredin the
“
Quickinfo
”
menu group
rst.
The
“
PIN Lock
”
is reactivatedautomatically after 15 seconds have passedwithout a
key being pressed. Alternatively by entering the PIN
|
0000
|
or cutting off the power
supply.
7.13.6
Comparison of two sensor values
Tow sensor values per stall are comparedconstantly andcheckedfor plausibility to increase the
operational reliability.
Sensor diff. time
Sensor diff. time
Temperature sensor difference time until fault
If the difference between the sensor values persists for the duration of the time set
here, the fault message
“
Sensor Diff.
”
is output.
Setting range: 1...250 min.
Factory setting: 10 min.
Sensor diff.max
Sensor diff.max
Difference between the two sensor values in the stall.
If the difference between the two sensor measured values exceeds the value set here
a fault message is output with a delay (setting:
“
sensor diff. time
”
).
This function only becomes active at settings
above 0.0 K
!
Setting range: 0.0...20.0 K
Factory setting: 0.0 K
7.13.7
Temperature monitoring by distance alarms (relative to nominal value)
The temperature can be monitoredto absolute values or alternatively to relative values in relation to
the currently active nominal value (distance alarm).
Distance alarm
Distance alarm
OFF
= temperature monitoring to absolute values
(at factory)
ON
= temperature monitoring to relative values in relation to the currently active
nominal value (distance alarm).
Automatic nominal value changes which can result from the
“
automatic reduction
”
and
“
growth curves
”
functions are considered.
Settings of the alarm limits
Setting of the temperature monitoring
“
Alarm Minimum
”
and
“
Alarm Maximum
”
.
7.14
|
Installation
|
Measuring fan
◄
Measuring fan
↑
|
ESC
|
P
↓
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
43/83