6.2 Main switch (only Type PTE-6/10AHQ(X)-L)
0
Power stack (fan) is switchedoff
Auto
Power stack in operation (standard position)
100 %
Fans are running with line voltage
Information
The display is in operation in every switch position! (cannot be switched off)
The function of the switch for the control unit can be changed in the Installation menu -
“
Diverse
”
- Switch mode.
•
Switch mode
“
OFF
”
(factory setting).
The control unit is active in all switch positions, overtemperature/undertemperature messages,
shutter control etc. also in switch position
“
0
”
and
“
100%
”
!
•
Switch mode
“
ON
”
In switch position
“
0
”
and
“
100%
”
the control unit is switchedoff andbehaves passively (Stop
symbol in display).
6.3 Menuoperation
The menu group is selectedwith the rotary
knob starting from the Overview display. The
triangle shows the menu group, for
“
Ventila-
tion
”
, for example, this is underneath the sym-
bol for fan andshutter.
By pushing the
P
button, one reaches individu-
al menu items in the menu group (e.g. to
“
PIN
”
,
“
Setpoint
”
etc.).
One moves up anddown within the menu
group using the rotary button.
After selecting the menu item, the
P
key is
pressedto make settings.
If the previously set value starts to
ash, it can
be adjusted with the rotary button and then
savedwith the
P
key.
To exit the menu without making any changes,
use the
|
Esc
|
key, i.e., the originally set values
remain.
One returns to the level menu group
“
Ventila-
tion
”
using the
|
ESC
|
key.
Overview display
S:20.0
°
SH:94%
Ventilation
↑
|
ESC
|
P
↓
↑
|
ESC
|
P
↓
PIN
Setpoint
↑
↓
↑
↓
Setpoint
Pband
Operating Instructions
UNIcon / Acontrol
Controls andMenu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB