Operation manual
www.zigor.com
35
OTHERS
UPS topology
Online, Doble-convertion, PFC, PWM Controlled, tower format
Efficiency
Up to 88%
Up to 90%
Up to 92%
Cold-start
Yes
Re-start
Yes
Communications
Standard: USB and RS232 ports
Optional: SNMP/Modbus TCP or dry contact cards
Battery test function
Yes
Control panel
LCD display and LED indicatorsa
Alarms
AC input abnormal, low battery, overload, failure
Protect function
Battery low voltage, overload, over-temperature, shortcircuit, output over/low voltage
Protection degree
IP20
Cooling
Forced ventilation
Noise level
< 50 dBA (@ 1 m)
Working temperature
0 ~ 40 ºC
Storage temperature
-25 ~ 55 ºC
Relative humidity
20 ~ 90 % (without condensation)
Altitude
< 1500 m (without power reduction)
Dimensions (W × H × D)
145 x 215 x
300 mm
145 x 215 x
300 mm
192 x 335 x
470 mm
192 x 335 x
470 mm
192 x 335 x
470 mm
192 x 335 x
470 mm
Weight
9,2 kg
4,3 kg
19,5 kg
7,8 kg
26,5 kg
8,4 kg
External battery cabinet*
Dimensions (W × H × D)
NA
145 x 215x
400 mm
NA
192 x 335x
470 mm
NA
192 x 335x
470 mm
Weight w/o batteries
4,2 kg
7,6 kg
7,9 kg
•
Other battery cabinet sizes could be used in case of bigger battery and/or autonomy.
•
The technical specifications may be modified without prior notice.
•
For any other technical need or modification of existing ones, consult ZIGOR.