Operation manual
www.zigor.com
14
Follow carefully the steps below:
•
Make sure that the UPS is completely switched off and disconnected from the mains supply before
adding the batteries.
•
Check the voltage of each battery.
•
Assemble the battery cabinet(s) in accordance with the instructions included with the cabinet. Remember
to leave a minimum distance of 500mm between a lateral panel of each battery cabin and the obstacles
there may be around the battery cabinet. In this way, assembly and maintenance of the batteries are
easier.
•
Install the breaker in accordance with the instructions included with the battery cabinet and check it is
open.
•
Place and wire the batteries distributed over the cabinet divisions in accordance with the included battery
assemble drawing.
•
Connect the battery cabinet(s) to the corresponding UPS terminals.
Fig. 3-3 Battery connection example with A type cabinets
•
Check total voltage and polarity of each battery string is correct.
In case of doubt, contact our customer service ([email protected]).
UPS
Battery
cabinet
WARNING
Be careful to check battery connector voltage and battery pack voltage. It must be the same.
Each UPS has its own optimized design battery bus voltage.
Check printed voltage under connector on rear panel before connecting battery pack.