CHOOSING THE CORRECT BATTERY SIZE
The Premier Power Pack power supplies can use a wide range of battery sizes.
To help determine the most suitable battery size, the following points need to be considered:-
1.
What will be the normal operating output current of the PSU. Will it be a high load (e.g. door holders),
or a small load (e.g. a sounder circuit controller)
2.
What will be the alarm load?
3.
What is the required standby time?
4.
What is the required alarm time?
In general, applications with a higher quiescent current load will require bigger batteries, if they also require a
high standby time.
Typical Battery requirements for a Power Pack 5.0A Power supply
APPLICATION
CURRENT LOAD
STANDBY
REQUIRED AMP
HOUR
TYPICAL
BATTS
CHARGE IN
EN54 TIME
Auto Dialler
50 / 100 mA
72 Hours
4.5 Ah
7 Ah
Yes
GSM Com
200 / 500 mA
48 Hours
12.3 Ah
12 Ah
Yes
Door holders
2 A load
24 Hours
60 Ah
60 Ah
NO
Door holders
2 A load
2 Hours
5 Ah
7 Ah
Yes
Door holders
4 A load
2 Hours
10 Ah
12Ah
Yes
ZSCC (1 unit)
40mA / 1A
24 Hour
1.8 Ah
2.2 Ah
Yes
ZSCC (5 units)
200mA / 5A
24 Hours
9.2 Ah
12 Ah
Yes
FyreSense
Aspiration Unit
500mA
24 Hours
15.3 Ah
17 Ah
Yes