PREMIER POWER PACK INSTRUCTION MANUAL 

 

GLT.MAN-138 

 

PAGE 2

 

Issue: 1.13    27/7/2012    N.R.P.J.

 

 

INTRODUCTION TO THE PREMIER POWER PACK PSU 

The Premier Power Pack is an EN54 compliant Power Supply, intended to power ancillary fire alarm equipment. 
 
It incorporates a small LCD screen that will give information about the Power Supply status (such as output 
voltage, output current, charger voltage etc). 
 
It also displays basic information via its LEDs (Power/General fault / earth fault & Battery fault). These LEDs are 
located on the panel door, and also on the controller PCB itself. 
 
The power supply has a 3 state charger. It will initially supply a BOOST charge current, until it has detected that 
the battery is close to full charge, then it will switch to FLOAT charging. If it detects flat or missing batteries, it will 
switch to PULSE mode, until it detects good batteries. 
 
The PSU monitors batteries for High Internal resistance, and will report a fault if it detects a resistance that would 
prevent the PSU giving its rated output. 
 
The power supply will prevent battery deep discharge by disconnecting the batteries when they reach their final 
voltage under a mains fail condition. 
 
The Power pack PSU is also available as a “CIE version”, used to power fire alarm panels. This version of the PSU is 
normally supplied without the current measuring feature. 
 
The “Control panel” version does not have the LCD fitted, so will communicate its status via its internal LEDs only.  
 

 

 

 

Содержание Premier Power Pack

Страница 1: ...PREMIER POWER PACK INSTRUCTION MANUAL GLT MAN 138 Issue 1 13 27 7 2012 N R P J EN54 4 POWER SUPPLY UNIT INSTRUCTION MANUAL...

Страница 2: ...4 LCD 4 LED External 5 LED Internal 5 Mounting the Power Supply 6 Electrical Connections 7 Electrical Safety Measures 7 Batteries 7 Connecting the Mains Battery 8 Connecting Ancillary Equipment to the...

Страница 3: ...ply a BOOST charge current until it has detected that the battery is close to full charge then it will switch to FLOAT charging If it detects flat or missing batteries it will switch to PULSE mode unt...

Страница 4: ...ply running on batteries only could not supply it s rated load For Example if a 5 Amp power supply has batteries with 2 ohms internal resistance when running on batteries and supplying full load there...

Страница 5: ...T T S O K V A 2 9 5 V B 2 9 5 V C U R R E N T 0 1 2 A M P S This screen shows whether mains and battery are OK or BAD It also shows the output voltage and the current being supplied In the event of a...

Страница 6: ...vel shows the battery internal resistance that would cause the power supply to report a fault Screen 5 Software Version Info S o f t W a r e P S U 2 V 1 0 S o f t W a r e L C D 1 V 0 0 This screen sho...

Страница 7: ...mier Power Pack to a suitable sturdy Flat surface Fitting the PSU at eye level will allow the panel s display to be easily read Use Fixing screws suitable for the chosen surface remembering that with...

Страница 8: ...ors on the power supply cage must be insulated using the provided plastic cover After locking the access door the key MUST be removed and ONLY held by the responsible person and or the service personn...

Страница 9: ...ed to the PSU Cage The Live Earth and Neutral connections are marked on the switch mode cage The incoming mains cable should be kept separate from the other cables to help minimise mains interference...

Страница 10: ...e to the Power Supply For 7 Ah 12 Ah Batteries Power Pack 2 0 For 17 Ah Batteries Power Pack 5 0 The Recommended Battery types are POWER SUPPLY VERSION MINIMUM RECOMMENDED SIZE MAXIMUM RECOMMENDED SIZ...

Страница 11: ...used The Positives should be commoned together as shown The Negatives are already commoned on the controller PCB so do not need to be commoned externally Connect to a single output if the maximum curr...

Страница 12: ...turn off its battery charger when the batteries are disconnected To check the charger voltage it will be necessary to set the unit into configuration mode To do this 1 Disconnect batteries turn off ma...

Страница 13: ...time 4 What is the required alarm time In general applications with a higher quiescent current load will require bigger batteries if they also require a high standby time Typical Battery requirements...

Страница 14: ...1A BATTERY BACKUP Battery type 2 x 12V Sealed Lead Acid Batteries connected in SERIES 2 x 12V Sealed Lead Acid Batteries connected in SERIES Battery Size Range 7 0 17 Ah 2 0 12 Ah Charger Type CPU con...

Страница 15: ...verload protection 110 150 110 150 Overload protection Type Hiccup mode automatic recovery Hiccup mode automatic recovery Over voltage protection 33 35 39 15V 33 5 39V Over voltage protection Type Hic...

Страница 16: ...y leads is disconnected MANUFACTURER S DECLARATION I hereby declare that the design of the 5A Premier Powerpack PSE has been carried out in accordance with a quality management system which incorporat...