PREMIER POWER PACK INSTRUCTION MANUAL 

 

GLT.MAN-138 

 

PAGE 15

 

Issue: 1.13    27/7/2012    N.R.P.J.

 

 

MAINTENANCE INFORMATION 

 
The following maintenance should be carried out at least once per annum: 
 

a)

 

Check that the output voltage of both outputs is within the range specified in the Technical Information 
section; 

b)

 

Check the charger voltage using the instructions in this manual; 

c)

 

Check the battery condition. Look for signs of leakage or corrosion. Make sure that the battery leads 
are securely attached to the battery terminals; 

d)

 

Check for damage to the insulation of all electrical cables; 

e)

 

Check that a fault is reported when the AC mains are switched off; 

f)

 

Check that a fault is reported when one of the battery leads is disconnected. 

MANUFACTURER'S DECLARATION 

 

I hereby declare that the design of the 5A Premier Powerpack PSE has been carried out in accordance with a 
quality management system which incorporates a set of rules for the design of all elements of the PSE; 
 
and the components of the 5A Premier Powerpack PSE have been selected for the intended purpose and are 
expected to operate within their specification when the environmental conditions outside the cabinet of the PSE 
conform to class 3K5 of EN 60721-3-3:1995. 
 

Geoff Walker 

Approvals Manager 
GLT Exports Limited 
 

1

st

 July 2011 

 

 

0359 

 

Zeta Alarm Systems by GLT Exports Ltd,  

72-78 Morfa Road, Swansea SA1 2EN 

 

12 

 

0359-CPD-0146 

 
 

EN54-4:1997+A1:2002 + A2: 2006 

 
 

Power supply equipment for fire detection and fire 

alarm systems for buildings 

 

Premier PowerPack 

PP2/12, PP5/17 

 

Other Technical Data: See Doc: “Simplicity Plus Product file” 

 held by the manufacturer 

 

 

Содержание Premier Power Pack

Страница 1: ...PREMIER POWER PACK INSTRUCTION MANUAL GLT MAN 138 Issue 1 13 27 7 2012 N R P J EN54 4 POWER SUPPLY UNIT INSTRUCTION MANUAL...

Страница 2: ...4 LCD 4 LED External 5 LED Internal 5 Mounting the Power Supply 6 Electrical Connections 7 Electrical Safety Measures 7 Batteries 7 Connecting the Mains Battery 8 Connecting Ancillary Equipment to the...

Страница 3: ...ply a BOOST charge current until it has detected that the battery is close to full charge then it will switch to FLOAT charging If it detects flat or missing batteries it will switch to PULSE mode unt...

Страница 4: ...ply running on batteries only could not supply it s rated load For Example if a 5 Amp power supply has batteries with 2 ohms internal resistance when running on batteries and supplying full load there...

Страница 5: ...T T S O K V A 2 9 5 V B 2 9 5 V C U R R E N T 0 1 2 A M P S This screen shows whether mains and battery are OK or BAD It also shows the output voltage and the current being supplied In the event of a...

Страница 6: ...vel shows the battery internal resistance that would cause the power supply to report a fault Screen 5 Software Version Info S o f t W a r e P S U 2 V 1 0 S o f t W a r e L C D 1 V 0 0 This screen sho...

Страница 7: ...mier Power Pack to a suitable sturdy Flat surface Fitting the PSU at eye level will allow the panel s display to be easily read Use Fixing screws suitable for the chosen surface remembering that with...

Страница 8: ...ors on the power supply cage must be insulated using the provided plastic cover After locking the access door the key MUST be removed and ONLY held by the responsible person and or the service personn...

Страница 9: ...ed to the PSU Cage The Live Earth and Neutral connections are marked on the switch mode cage The incoming mains cable should be kept separate from the other cables to help minimise mains interference...

Страница 10: ...e to the Power Supply For 7 Ah 12 Ah Batteries Power Pack 2 0 For 17 Ah Batteries Power Pack 5 0 The Recommended Battery types are POWER SUPPLY VERSION MINIMUM RECOMMENDED SIZE MAXIMUM RECOMMENDED SIZ...

Страница 11: ...used The Positives should be commoned together as shown The Negatives are already commoned on the controller PCB so do not need to be commoned externally Connect to a single output if the maximum curr...

Страница 12: ...turn off its battery charger when the batteries are disconnected To check the charger voltage it will be necessary to set the unit into configuration mode To do this 1 Disconnect batteries turn off ma...

Страница 13: ...time 4 What is the required alarm time In general applications with a higher quiescent current load will require bigger batteries if they also require a high standby time Typical Battery requirements...

Страница 14: ...1A BATTERY BACKUP Battery type 2 x 12V Sealed Lead Acid Batteries connected in SERIES 2 x 12V Sealed Lead Acid Batteries connected in SERIES Battery Size Range 7 0 17 Ah 2 0 12 Ah Charger Type CPU con...

Страница 15: ...verload protection 110 150 110 150 Overload protection Type Hiccup mode automatic recovery Hiccup mode automatic recovery Over voltage protection 33 35 39 15V 33 5 39V Over voltage protection Type Hic...

Страница 16: ...y leads is disconnected MANUFACTURER S DECLARATION I hereby declare that the design of the 5A Premier Powerpack PSE has been carried out in accordance with a quality management system which incorporat...

Отзывы: