28 - D2O VCP Product Manual
COMMAND SYNTAX
DETAILS
inp -z
<confirm>
Resets the total accumulated pulse counter to zero. Enter
CLEAR
at
<confirm>
to avoid
accidental use.
This is an
Admin Restricted c
ommand and cannot be set until the
admin
command has
been executed.
Example:
inp -z CLEAR
OK
COMMAND SYNTAX
DETAILS
inp -v
[F]
Displays the last recorded analogue input reading in either mV or µA (settings dependent).
The optional parameter F can be entered at [F] to make the D2O take a new measurement
instead of displaying the last recorded measurement.
Example: Display a new analogue input reading from the D2O, when it is setup to take a 0 to 5V input.
inp -v F
Voltage Input: 3796 mV
COMMAND SYNTAX
DETAILS
inp -p
Displays the present pulse counter reading. This is a cumulative reading that includes all
readings ever recorded by the D2O since initial deployment, or since the counter has been
manually cleared.
Example:
inp -p
Pulse Counts: 2142
COMMAND SYNTAX
DETAILS
inp -o
<±20000>
Sets the analogue input electrical offset compensation in µV or µA (matched to the selected
input type). The parameter at
<±20000>
can be set between
-20000
to
20000
.
This
provides a means to calibrate or tune the measured input reading to match what is
expected from the connected device.
This is an
Admin Restricted c
ommand and cannot be set until the
admin
command has
been executed.
Example: Needing to add +1200µV to the measured input reading, in a scenario where the D2O is setup to take a 0 to 5V analogue input.
inp -o 1200
OK