D2O VCP Product Manual - 27
COMMAND SYNTAX
DETAILS
msg -g
Displays the date and time in Greenwich Mean Time (GMT) of the next satellite transmission
opportunity within a 24 hour window from now.
The returned date and time format is: Weekday Day - Month - Year Hour : Minute : Second
While this is the next opportunity it does not guarantee a successful transmission will occur.
Factors such as physical obstructions, interference or inclement weather can prevent a
successful transmission from occurring.
Example:
msg -g
Thursday 07-01-2021 11:54:22
COMMAND SYNTAX
DETAILS
inp -a
<on> <off>
This command provides a method to control the D2O’s digital output signal, based on the
present analogue input readings. It uses an on and off threshold setting to determine when
the digital output signal should be set to
ON
.
The parameters at
<on>
and
<off>
are percentages of the analogue input’s range (0 -
100%). For example a reading of 1V would equate to 20% of a 0 to 5V input range if the D2O
was configured that way. Setting both parameters to
0
disables the feature (default setting).
The threshold logic will automatically adjust to suit scenarios where the
ON
value is either
higher or lower than the
OFF
value.
This is an
Admin Restricted c
ommand and cannot be set until the
admin
command has
been executed.
Example: A scenario where the digital output should be set to
ON
when the input reading is at 20% of its range, and
OFF
when the input
reading is at 60% of its range.
inp -a 20 60
OK
COMMAND SYNTAX
DETAILS
inp -s
<1 to 3>
Sets the amount of smoothing applied to a recorded measurement of the analogue input.
This is a very application dependent setting, and it is recommended to experiment with the
setting to determine if the reading produced is as desired.
It effectively produces an averaged result from several measurement samples taken in
very quick succession (all readings in <1 second). This provides a more representative and
reliable measurement by compensating for minor fluctuations, interferences or anomalies
that may occur when conducting a single measurement. The parameter can be set to:
1
Average of 4 sample readings (default) - suitable for most scenarios and devices
2
Average of 8 sample readings
3
Average of 16 sample readings
This is an
Admin Restricted c
ommand and cannot be set until the
admin
command has
been executed.
Example: Setting the smoothing level of a recorded input measurement to be 2.
inp -s 2
OK