© 2013/EN Zep Solar, Inc. reserves the right to make specifications changes without any prior notice. All rights reserved.
www.zepsolar.com
Document #800-0329-001 Rev F
File Generated July 3, 2013
Page 30
ZS SPAN INSTALLATION MANUAL FOR RAIL-BASED APPLICATIONS - U.S.
Along the axis of the Interlock, large arrays also need a physical gap after two Thermal Expansion
Joints. For example, a North-South drop-in, Landscape orientation, might require a physical gap
approximately every 100 feet. This would be approximately every 18 module lengths, depending
on the module.
Figure 4.14 Large Array, North Drop-In, Thermal Expansion Gap
4.5 Roof Zones
Roof zones identify the interior, edge and corner regions of each designated roof plane. This is to
take into account varying wind pressures as the wind passes over different areas of the roof. The
maximum allowable Cam Foot spacing may be smaller in edge and corner roof zones.
Note:
The examples shown in this document are for illustration purposes only and are subject to
change in accordance with any modifications to regional engineering and structural requirements.
6
6
6
6
10
10
Every third joint should be a
physical gap recommended
minimum 12 inches
Thermal Expansion Joints