Touch-MyDesign Plus
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
56
Shutter / Step Down
1 Bit
E
C T - W -
DPT_Switch
0/1
-
-
[Zn] Two Objects, Long Press: "0"
1-bit Generic Control
1 Bit
E
C T - W -
DPT_Switch
0/1
-
-
[Zn] Two Objects, Long Press: "1"
1-bit Generic Control
1 Bit
E
C T - W -
DPT_Switch
0/1
-
-
[Zn] Two Objects, Long Press: "0/1"
1-bit Generic Control
1 Bit
E
C T - W -
DPT_Trigger
0/1
-
-
[Zn] Stop Shutter
0, 1 = Stop Shutter
56, 61, 66, 71,
76
4 Bit
E
C T - W -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec.by 100%)
…
0x8 (Stop)
0x9 (Inc.by 100%)
…
0xF (Inc.by 1%)
-
-
[Zn] Light Dimming (Toggle)
4-bit Dimming Control
57, 62, 67, 72,
77
2 Bytes
E
C T - W -
DPT_Value_Temp
-273.00°C
- 670760.00°C
-
-
[Z] Temperature Setpoint
-20.0°C – 150.0°C
1 Byte
E
C T - W -
DPT_Value_1_Ucount
0 - 255
-
-
[Z] 1-byte Value (Unsigned Int)
0 – 255
1 Byte
E
C T - W -
DPT_Scaling
0% - 100%
-
-
[Z] 1-byte Value (Scaling)
0 – 100%
2 Bytes
E
C T - W -
DPT_Value_2_Ucount
0 - 65535
-
-
[Zn] 2-byte Value (Unsigned Int)
0 – 65535
1 Byte
E
C T - W -
DPT_Value_1_Ucount
0 - 255
-
-
[Zn] 1-byte Value (Unsigned Int)
0 – 255
1 Byte
E
C T - W -
DPT_Scaling
0% - 100%
-
-
[Zn] 1-byte Value (Scaling)
0 – 100 %
2 Bytes
E
C T - W -
9.xxx
-671088.64 -
670760.96
-
-
[Zn] 2-byte Value (Float)
-671 088.64 – 670 760.96
1 Byte
E
C - - W -
DPT_Scaling
0% - 100%
-
-
[Zn] Light Dimming (Status)
0 – 100 %
1 Byte
E
C - - W -
DPT_Scaling
0% - 100%
-
-
[Zn] Shutter Position
0 – 100 %
1 Byte
E
C T - W -
DPT_Value_1_Count
-128 - 127
-
-
[Zn] 1-byte Value (Signed Int)
-128 - 127
2 Bytes
E
C T - W -
DPT_Value_2_Count
-32768 - 32767
-
-
[Zn] 2-byte Value (Signed Int)
-32768 - 32767
58, 63, 68, 73,
78
1 Bit
E
C - - W -
DPT_Switch
0/1
-
-
[Zn] LED On/Off
0 = On; 1 = Off
1 Bit
E
C - - W -
DPT_Switch
0/1
-
-
[Zn] LED On/Off
0 = Off; 1 = On
79, 83
2 Bytes
S
C T R - -
DPT_Value_Temp
-273.00°C –
670760.00°C
-
-
[In] Current Temperature
Temperature sensor value
80, 84
1 Bit
S
C T R - -
DPT_Alarm
0/1
-
-
[In] Overcooling
0 = No Alarm;1 = Alarm
81, 85
1 Bit
S
C T R - -
DPT_Alarm
0/1
-
-
[In] Overheating
0 = No Alarm;1 = Alarm
82, 86
1 Bit
S
C T R - -
DPT_Alarm
0/1
-
-
[In] Probe Error
0 = No Alarm;1 = Alarm
87
2 Bytes
S
C T R - -
DPT_Value_Temp
-273.00°C –
670760.00°C
-
-
[Internal Sensor] Current Temperature
Temperature sensor value
88
1 Bit
S
C T R - -
DPT_Alarm
0/1
-
-
[Internal Sensor] Overcooling
0 = No Alarm;1 = Alarm
89
1 Bit
S
C T R - -
DPT_Alarm
0/1
-
-
[Internal Sensor] Overheating
0 = No Alarm;1 = Alarm
91, 97
1 Bit
E
C - - W -
DPT_Switch
0/1
-
-
[In] Input Lock
1 = Locked; 0 = Unlocked
92, 98
1 Bit
C T - - -
DPT_Switch
0/1
-
-
[In] [Short Press] 0
Sending of 0
1 Bit
C T - - -
DPT_Switch
0/1
-
-
[In] [Short Press] 1
Sending of 1
1 Bit
E
C T - W -
DPT_Switch
0/1
-
-
[In] [Short Press] 0/1 Switching
Switching 0/1
1 Bit
C T - - -
DPT_UpDown
0/1
-
-
[In] [Short Press] Move Up Shutter
Sending of 0 (Up)
1 Bit
C T - - -
DPT_UpDown
0/1
-
-
[In] [Short Press] Move Down Shutter
Sending of 1 (Down)
1 Bit
C T - - -
DPT_UpDown
0/1
-
-
[In] [Short Press] Move Up/Down Shutter
Switching 0/1 (Up/Down)