Square TMD
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
52
sensor
121, 145,
126, 150,
131, 155
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix][Cy] Detection State
(Scaling)
0-100%
122, 146,
127, 151,
132, 156
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Ix][Cy]
Detection State
(HVAC)
Auto, Comfort, Standby, Economy, Building
Protection
123, 147,
128, 152,
133, 157
1 Bit
O
C T R - -
DPT_Switch
0/1
[Ix][Cy] Detection State
(Binary)
Binary Value
124, 148,
129, 153,
134, 158
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix][Cy] Channel Lock
According to parameters
125, 149,
130, 154,
135, 159
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix][Cy] Force State
0 = No Detection; 1 = Detection
160, 166
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] Input Lock
1 = Locked; 0 = Unlocked
161, 167
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Short Press] 0
Sending of 0
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Short Press] 1
Sending of 1
1 Bit
I
C T - W -
DPT_Switch
0/1
[Ix] [Short Press] 0/1
Switching
Switching 0/1
1 Bit
C T - - -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up
Shutter
Sending of 0 (Up)
1 Bit
C T - - -
DPT_UpDown
0/1
[Ix] [Short Press] Move Down
Shutter
Sending of 1 (Down)
1 Bit
C T - - -
DPT_UpDown
0/1
[Ix] [Short Press] Move
Up/Down Shutter
Switching 0/1 (Up/Down)
1 Bit
C T - - -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step
Up Shutter
Sending of 0 (Stop/Step up)
1 Bit
C T - - -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step
Down Shutter
Sending of 1 (Stop/Step down)
1 Bit
C T - - -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step
Shutter (switched)
Switching of 0/1 (Stop/Step up/down)
4 Bit
C T - - -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
…
0x7 (Dec. by 1%)
0x8 (Stop)
0x9 (Inc. by 100%)
…
[Ix] [Short Press] Brighter
Increase Brightness