Securel v3
Technical Support:
16
Test On Mode
After entering the Test On mode, it will only be possible to control the door opening
through the on-board
“LOCK” pushbutton. Orders received through communication
objects will be ignored.
The action on the
“LOCK” button will cause the
door opening during the time it is
pressed
. Releasing the button will release the relay, causing the door to close.
As described previously if the device is in Test On mode, any command sent from the
KNX bus to the actuator will not affect the door opening (only periodically timed objects
such as Heartbeat will continue to be sent to the bus) while Test ON mode is active.
However, in the case of the
“Lock” objects, although in Test ON mode the actions
received by each object are not taken into account, the evaluation of their status is
carried out when exiting this mode, so that any change in the alarm status or blocking
of the outputs while Test ON mode is active is taken into account when exiting this
mode and is updated with the last status detected.
Important
:
the device is delivered from factory with all the outputs disabled, and with
both manual modes (Test Off and Test On) enabled
.
ETS PARAMETERISATION
The
Manual Control,
enabled by default in section 2.1,
is configured from the
“Configuration” tab itself under “Manual Control”.
Figure 7.
Manual Control
The only two parameters are:
Manual Control
[
Disabled / Only Test Off Mode / Only Test On Mode /
Test
Off Mode + Test On Mode
]. Depending on the selection, the device will permit
using the manual control under the Test Off, the Test On, or both modes.
Note that, as stated before, using the Test Off mode does not require any