Force medium fan under

: sets the minimum number of grilles that must 

be open before it is permitted to commute from the medium fan speed to 
the maximum fan speed  (object "A/C unit  -  Fan  status" will reflect the 
current fan level; see Table 1). 

Initial speed percentage 

Interpolated speed percentage 

Level 

0% 

0% 

Auto 

1-33% 

33% 

Minimum 

34-66% 

66% 

Medium 

67-100% 

100% 

Maximum 

Table 1. 

Fan speed percentages

 

 

Step control

:

 

selecting this option ("Yes") brings the 1-bit object "A/C unit - 

Fan  step", which allows increasing (sending the value "1") or decreasing 
(value "0") the fan speed by one level (for example, under the minimum level 
of speed, if the value "1" is sent via this fan step object, the speed will 
become medium). 

 

Precise control

:  selecting this option ("Yes")  brings  the 1-byte object "A/C 

unit - Fan precise", which allows establishing the value, in percentage, of the 
desired fan speed level, according to the values shown in Table 1. 

Step control and Precise control can be jointly enabled, so that the fan speed can be 
controlled in one manner or other at any time, as desired. 

3.5

 

TEMPERATURE 

From this window it is possible to configure several parameters related to the setpoint 
temperature sent to the A/C Unit.  

Note that the parameters shown below do not apply in modes “Auto”, “Fan” or “Dry”. 

Содержание IRSC Zone

Страница 1: ...IRSC Zone Zone Climate Controller ZN1CL IRSC USER MANUAL Application program version 1 7 User manual edition 1 7 _a www zennio com...

Страница 2: ...am 6 2 Configuration 8 2 1 General concepts 8 3 ETS Parametrization 9 3 1 Default configuration 9 3 2 General 11 3 3 Mode 14 3 4 Fan 16 3 5 Temperature 17 3 6 Thermostat 20 3 7 Reset 21 Annex I Instal...

Страница 3: ...of the device such as when both the normal mode and the extended mode read requests receive a response Implementation of the temperature restriction even when the machine is off not only when it gets...

Страница 4: ...functions into the same device Control of the main functionalities of A C units On Off temperature mode fan speed etc Compatibility with most air conditioning manufacturers please refer to the corresp...

Страница 5: ...e associated LED 2 light in red If this button is held while plugging the device into the KNX bus IRSC goes into secure mode IR emitter 5 infrared flashing diode to send commands to the air conditioni...

Страница 6: ...zones where the air output is regulated by gates or motorised grilles Grilles are the final elements of the air ducts in charge of distributing the air from the central unit to every zone and permit...

Страница 7: ...hough the ambient temperatures of the zones are not Moreover this calculation will also consider any addition temperature other than zero that may have been parameterised see Section 3 5 Apart from se...

Страница 8: ...cting the number of the zones of the KNX installation that will be controlled by the same central A C machine which can be 1 8 Moreover the following functionalities of the A C system can be controlle...

Страница 9: ...rameterization starts from for the first time Figure 4 IRSC Zone Default topology The following communication objects appear A C Unit ON OFF status A C Unit Setpoint status and A C Unit fan status all...

Страница 10: ...control sends orders 0 Close 1 Open to the bus to control the airing grille of the corresponding zone Zone X Grille Status Reception permits the arrival from the bus of open close orders for the airin...

Страница 11: ...rameter download All the aforementioned tabs are explained in detail in the next sections 3 2 GENERAL As shown in Figure 5 from the General window it is possible to configure the main parameters of th...

Страница 12: ...rmitted number of closed grilles from 0 to 8 before an order to open the bypass is forced via the object Additional bypass In other words the bypass will stay open while the number of open grilles is...

Страница 13: ...terfaces such as the InZennio Z41 touch pannel that let the user set those values and therefore make IRSC Zone aware of them It is recommended however to enable sending the statuses to the bus on star...

Страница 14: ...tion 3 6 as well as Annex II Grille control and Annex III Practical example In relation to the calculation of the general setpoint mode Cold implies on the one hand switching from one range of accepte...

Страница 15: ...commutation from one mode to another will be performed Figure 6 Mode window Individual control when this option is selected all the described working modes will be selectable through one specific 1 b...

Страница 16: ...ntrol In addition section 3 5 and Annex III Practical example explain the calculation process of the general setpoint based on the zone setpoint temperatures and the current working mode 3 4 FAN The F...

Страница 17: ...creasing sending the value 1 or decreasing value 0 the fan speed by one level for example under the minimum level of speed if the value 1 is sent via this fan step object the speed will become medium...

Страница 18: ...comes available with value 1 by default Temperatures will be subject to the above limits only while the value of this object is 1 The value 0 on the other hand means that the parameterised restriction...

Страница 19: ...at are ON at that moment If the return temperature is higher mode Heat or lower mode Cool than the desired temperatures for the zones IRSC Zone will require the machine to make an extra effort and wil...

Страница 20: ...of not enabling a certain thermostatic control the one for cooling the one for heating or both the status of the grilles will be determined by the status of their zone zone ON grille open zone OFF gri...

Страница 21: ...ion to grille control In addition to obtain detailed information about all these parameters related to the thermostatic control please refer to the specific document Zennio Thermostat Home available a...

Страница 22: ...ke IRSC Zone send read requests to the bus in order to get updated values of the objects that determine the initial state it should assume when it becomes functional Such option Zone update on start u...

Страница 23: ...installation by receiving data from an external touch panel InZennio Z38i or InZennio Z41 and from a sensor QUAD which measures the temperatures of the different enabled zones in the installation Wit...

Страница 24: ...e calculation is resumed according to the new mode and the new setpoint If on the contrary a zone switch off order arrives IRSC Zone will close the corresponding grille and will stop considering the s...

Страница 25: ...ol 0 the grille according to the diagram shown in Figure 13 Regarding the second method PI control it consists in the continuous execution of the PI control mathematic algorithm which permanently dete...

Страница 26: ...ecting between a 2 point with hysteresis control and a PI control with pulse width modulation In this case the flow diagram for the first one is as shown in Figure 14 Figure 14 Grille behaviour during...

Страница 27: ...Also assume that zone Z3 has been switched off and that a maximum temperature of 24 C has been parameterised for the Heat mode and that the Temperature restriction object has been previously assigned...

Страница 28: ...e External temperature returned 26 5 C IRSC Zone will then look for the maximum among the setpoint temperatures of zones Z1 and Z2 and afterwards for the maximum between this 25 C which is truncated t...

Страница 29: ...4 1 Bit I C T W U 1 001 DPT_Switch 0 1 Zone 2 ON OFF 0 Off 1 On 5 1 Bit I C T W U 1 001 DPT_Switch 0 1 Zone 3 ON OFF 0 Off 1 On 6 1 Bit I C T W U 1 001 DPT_Switch 0 1 Zone 4 ON OFF 0 Off 1 On 7 1 Bit...

Страница 30: ...C T R 9 001 DPT_Value_Temp 273 670760 24 Last Zone 7 Setpoint Status Setpoint Temperature 34 2 Bytes O C T R 9 001 DPT_Value_Temp 273 670760 24 Last Zone 8 Setpoint Status Setpoint Temperature 35 1 Bi...

Страница 31: ...Unit Modes Status 1byte Actual Mode 0 Auto 1 Heat etc 62 1 Bit I C T W U 1 17 DPT_Trigger 0 1 0 Last A C Unit Heat Mode 1 Set Heat mode 0 Nothing 63 1 Bit O C T R 1 17 DPT_Trigger 0 1 0 Last A C Unit...

Страница 32: ...your inquiries about Zennio devices http zennioenglish zendesk com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com...

Отзывы: