Unit ratings
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 30
The following tables provide the maximum motor FLC that should be used on each SS6000 model for specific
starting & operating duties.
15A – 80A with Integral Bypass Contactor (
380 - 415V)
Light Duty:
Standard
Duty:
Severe Duty:
Model
Chassis
Dimensions (mm)
15A
15A
15A
6R015B2
B2
335h 162w 174d
30A
25A
20A
6R030B2
B2
335h 162w 174d
60A
54A
44A
6R060B2
B3
440h 162w 174d
80A
70A
56A
6R080B2
B3
440h 162w 174d
220 -460V 3 Wire Bypass
Light Duty:
Standard Duty:
Severe Duty:
Model
Chassis
Dimensions (mm)
105
92
82
6R10000
A2
430h 248w 232d
193
170
151
6R19000
A2
430h 248w 232d
221
193
172
6R22000
A2
430h 248w 232d
367
321
285
6R36000
A3
670h 375w 285d
586
513
456
6R58000
A3
670h 375w 285d
830
806
716
6R83000
A3
670h 375w 285d
220 -460V 3 Wire Continuous
220 -460V 6 Wire Bypass (inside Delta Connection)
Light Duty:
Standard Duty:
Severe
Duty:
Model
Chassis
Dimensions
(mm)
180
159
140
6R10000
A2
430h 248w 232d
330
290
260
6R19000
A2
430h 248w 232d
380
330
295
6R22000
A2
430h 248w 232d
635
555
490
6R36000
A3
670h 375w 285d
1015
888
789
6R58000
A3
670h 375w 285d
1435
1395
1240
6R83000
A3
670h 375w 285d
Light Duty:
Standard Duty:
Severe Duty:
Model
Chassis
Dimensions (mm)
100
88
78
6R10000
A2
430h 248w 232d
178
157
141
6R19000
A2
430h 248w 232d
203
179
161
6R22000
A2
430h 248w 232d
341
302
270
6R36000
A3
670h 375w 285d
534
473
425
6R58000
A3
670h 375w 285d
796
710
641
6R83000
A3
670h 375w 285d
Содержание SMARTSTART 6000 Series
Страница 1: ...User s Manual SMARTSTART 6000 Series Models 6R15 6R830 6V400 6V630...
Страница 2: ......
Страница 39: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev D Page 36 General Purpose...
Страница 41: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev D Page 38 Irrigation Pump...