Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 23
R01 Manual Reset
Activate or de-activate the manual reset ie. The
reset on the local console.
Range:
Enable; Disable
Default:
Disable
To save changes
To exit without saving
R02 Power Reset
Activate or de-activate reset on removal of control
supply.
Range:
Enable; Disable
Default:
Enable
To save changes
To exit without saving
R03 Start Reset
Activate or de-activate reset on a start command.
Range:
Enable; Disable
Default:
Disabled
To save changes
To exit without saving
A10 Kick Start
Set to provide a kick during starting. This provides
an adjustable torque boost to the motor when a
start is initiated. This will also result in a higher
start current during the kick duration.
When a kick time of 0.0 seconds is selected
‘Disabled’ will be displayed.
To enter submenu to modify
To exit sub menu
A11 Kick Time
Set to the time of the kick
Range:
0.0 – 2.0 seconds
Default: 0.0 (Disabled)
To save changes
To exit without saving
A12 Kick Level
Set the level of kick as a percentage % of
Locked Rotor Current.
Range:
50 – 100%
Default: 70%
To save changes
To exit without saving
A20 Accel Method
The acceleration method allows adjustment of the
aceleration profile and acceleration control. This
provides advanced control of the motor during the
ramp time to better match the type of load or
application.
See Appendix A on Page 34-35 for more details.
To enter submenu to modify
To exit sub menu
A21 Accel Profile
Select the type of acceleration profile to match
the type of load or application.
Example: Pump/Fan = Squared
Range:
Linear, Squared
Default: Squared
To save changes
To exit without saving
A22 Accel Control
Select the type of Acceleration control to suit the
load or application. Torque Control will provide
greater control of motor acceleration.
Range:
Torque; Voltage
Default: Torque
To save changes
To exit without saving
Setup Menu
8 Advanced
Setup Menu
7 Resets
Kick Time
Kick Level
A10 Kick Start
0.2s
70%
Accel Profile
Accel Control
A20 Accel Method
Squared
Torque