5.2 Preparations
Trouble-free operation of the lifting unit depends not least on a correct and impeccable
assembly. For this reason, the DIN EN 12056-4 gives the following recommendations:
1.
Rooms for sewage lifting units must be so large that next to and above all parts to
be operated and maintained a work room of at least 60 cm width or height must be
DYDLODEH7KHLQVWDOODWLRQURRPPXVWEHVXႈFLHQWO\LOOXPLQDWHGDQGZHOOYHQWLODWHG
2.
The set-up area must be horizontal and level. The set-up area must be suitable for
the weight of the lifting unit.
3.
For room drainage with faeces lifting units, a pump sump (= deepening in the
ground) has to be arranged. Installation of a drainage pump in the pump sump is
recommended.
4.
Lifting units have to be secured against buoyancy and twisting.
5.
All pipelines have to be laid in such a way that they can run empty on its own. Seen
LQÀRZGLUHFWLRQWKHOLQHVPXVWQRWEHQDUURZHG
6.
All line connections on sewage lifting units must be designed in a sound-insulated
DQGÀH[LEOHZD\7KHZHLJKWRIWKHOLQHVKDVWREHDEVRUEHGRQWKHSDUWRIWKHEXLOG
-
ing site.
7.
$VKXWRႇYDOYHKDVWREHDUUDQJHGRQWKHLQOHWVLGHDQGRQWKHSUHVVXUHVLGHEHKLQG
WKHEDFNÀRZSUHYHQWHU
8.
No other connections may be carried out on the pressure line. The minimum nominal
width of the pressure line is DN 80.
9.
The pressure line of the lifting unit has to be guided with a bend over the locally
VSHFL¿HGÀRRGOHYHO7KLVUHJXODWLRQLVDOVRDSSOLFDEOHWRWKHGUDLQDJHOLQHZLWKWKH
manual membrane pump and for the pressure line of the submersible pump in the
pump sump.
10. Pressure lines of sewage lifting units must not be connected to down pipes. They
must always be connected to vented manifolds or underground pipes.
11. Faeces lifting units have to be equipped with a check valve.
12.
7KHSUHVVXUHOLQHYROXPHDERYHWKHFKHFNYDOYHWRWKHEDFNÀRZORRSPXVWEHVPDOOHU
than the useful volume of the lifting unit. The useful volume of the lifting unit Kompak-
tboy Double ranges between 33 litres (lowest switch-on level) and 80 litres (highest-
possible switch-on level in case of inlet from above). 1 m pipeline DN 100 has a
content of approx. 8 l water.
13. Faeces lifting units are to be generally vented above the roof.
14.
,QGU\DQGZHOOYHQWLODWHGURRPVHOHFWULFDOGHYLFHVZKLFKDUHQRWÀRRGSURRIVXFKDV
VZLWFKER[HVDQGDODUPWUDQVPLWWHUVPXVWEHLQVWDOOHGÀRRGSURRI
15. Lifting units should not be operated in the vicinity of living and sleeping rooms.
16.
6XUIDFHZDWHUWKDWRFFXUVRXWVLGHWKHEXLOGLQJEHORZWKHÀRRGOHYHOKDVWREHFRQ
-
veyed separately from the domestic waste water and outside the building via a sew-
age lifting unit.
17. A manual membrane pump serves for easy drainage in case of trouble or power fail-
ure (not mandatory, but recommendable).
i
Содержание KOMPAKTBOY DOPPEL
Страница 21: ...Kompaktboy Doppel Deutsch 21 Einbaubeispiel zur Absch tzung des Platzbedarfs der Hebeanlage...
Страница 44: ...Kompaktboy Doppel Deutsch 44 9 2 1 Abmessungen Kompakboy Doppel 1 1 und 1 5...
Страница 45: ...Kompaktboy Doppel Deutsch 45 9 2 2 Abmessungen Kompakboy Doppel 3 0...
Страница 46: ...Kompaktboy Doppel Deutsch 46 10 Ersatzteilliste...
Страница 69: ...Kompaktboy Double en English 69 Assembly example for estimating the space requirement of the lifting unit...
Страница 92: ...Kompaktboy Double en English 92 9 2 1 Dimensions of the Kompaktboy Double 1 1 and 1 5...
Страница 93: ...Kompaktboy Double en English 93 9 2 2 Dimensions of the Kompaktboy Double 3 0...
Страница 94: ...Kompaktboy Double en English 94 10 List of spare parts...
Страница 117: ...Kompaktboy Double fr Fran ais Exemple d installation pour l estimation de l espace n cessaire la station de relevage...
Страница 140: ...Kompaktboy Double fr Fran ais 140 9 2 1 Dimensions Kompakboy Double 1 1 et 1 5...
Страница 141: ...Kompaktboy Double fr Fran ais 141 9 2 2 Dimensions Kompakboy Double 3 0...
Страница 142: ...Kompaktboy Double fr Fran ais 10 Liste de pi ces de rechange...