6.2 TESTER DESCRIPTION OF THE FUNCTIONS

The most important input or output signals can be measured in real time using the
TESTER function of the console. The Console acts as a multimeter able to read
voltage, current and temperature. The following definition listing shows the relative
measurements :

1) BATTERY VOLTAGE:

 level of battery voltage measured at the input to the key

switch.

2) MOTOR CURRENT:

 the current flowing in the drive motor armature.

3) FIELD CURRENT:

 the current flowing in the drive motor field winding.

4) VMN:

 the voltage effectively dropped across the MOS. It is measured between B-

and VMN.

5) TEMPERATURE:

 the temperature measured on the aluminum heat sink holding the

MOSFET devices.

6) ACCELERATOR:

 the voltage of the accelerator potentiometer wiper (CPOT).

The voltage level is shown on the Left Hand Side of the Console Display and the
value in percentage is shown on the Right Hand Side.

7) FORWARD SWITCH:

 the level of the Forward direction digital entry MA (pin B6).

ON /+ VB = active entry of closed switch.
OFF / GND = non active entry of open switch.

8) BACKWARD SWITCH:

 the level of the Reverse direction digital entry MI (pin B4).

ON /+ VB = active entry of closed switch.
OFF / GND = non active entry of open switch.

9) TILLER SWITCH:

  the level of the Handle/Seat Microswitch digital entry

(pin A4).
ON / + VB = active entry of closed seat switch.
OFF / GND = non active entry of open seat switch.

10) BELLY SWITCH:

 the level of the digital entry from Belly Button microswitch

(pin A5).
ON /+ VB = active entry, B SW closed.
OFF / GND = non active entry, B SW open.

11) DIGITAL INPUT #2 (A9):

 (only with option BACKING FUNCTION PROGRAMMED

OFF) the level of the auxiliary microswitch when used for speed reduction.
ON / GND= active entry of speed reduction microswitch.
OFF / +VB = non active entry of microswitch.

12) BACKING INPUT (A9):

 (only with option BACKING FUNCTION PROGRAMMED

ON) the level of auxiliary microswitch when used as backing enable.
ON / +VB = active.

13) HARD & SOFT (A8):

 level of the HARD & SOFT microswitch.

ON / +VB = active.

14) BATTERY CHARGE:

 battery charge indication %.

Содержание Chopper SEM-X

Страница 1: ...INSTALLATION AND USER MANUAL CHOPPER SEM X ELECTRONIC INDUSTRIAL DEVICES 42028 POVIGLIO R E Via Parma 59 ITALIA Tel 39 0522 960050 r a Fax 39 0522 960259 e mail zapi zapispa it...

Страница 2: ...ts via Console 15 4 2 Description of Console Connection 15 4 3 Description of Standard Console Menu 16 5 SEM X Cabling and Configuration 17 5 1 Power Diagram 17 5 2 Description of Programmable Functio...

Страница 3: ...Y N A P M O C S E C I V R E S T P E D Y N A P M O C E V I T U C E X E T N E M E G A N A M E V I T U C E X E T N E M E G A N A M E V I T U C E X E T N E M E G A N A M E V I T U C E X E T N E M E G A N...

Страница 4: ...actor NPC Negative Pump Contactor NPOT Negative Potentiometer PC Pump Contactor PEMB Positive Electromechanical Brake PEV Positive Lowering Valve PHORN Positive Horn PMC Positive Main Contactor PPC Po...

Страница 5: ...e end user Various chopper configurations can be selected by the user without the need for hardware modifications Future technological updates are made easy for the user The communication protocol wil...

Страница 6: ...C VERSIONS MAXIMUM CURRENT VOLTAGE DROP IN FULL CONDUCTION 24V 90A 3 0 14V at 35A 25 C 24V 110A 2 0 14V at 35A 25 C 2 2 CONTROL UNITS 2 2 a Microswitches Microswitches should have a contact resistanc...

Страница 7: ...on in either direction This function is unique when it is necessary to compensate for asymmetry with the mechanical elements associated with the potentiometer especially relating to the minimum level...

Страница 8: ...eration cannot commence if these operations are not carried out correctly Requests for drive must be made after closing the key Switch Protection against uncontrolled movements The Line Contactor will...

Страница 9: ...f the motor is rotating the chopper controls the speed and automatically brakes and keeps the motor at a very low speed during descent on a gradient This is a very useful safety feature and is not dri...

Страница 10: ...ure Battery Voltage Diagnosis is provided in 3 ways The Red Led connected to Connector B will flash a certain number of times for a given Alarm See Listings or the Digital Console may be used or MDI A...

Страница 11: ...a traction battery Do not use the outputs of converters or power supplies For special applications please contact the nearest Zapi service centre Start the machine the first time with the drive wheel...

Страница 12: ...connections to the motor armature and battery use cable of 10mm section For the Field connections use cable of 4mm section For the optimum chopper performance the cables to the battery should be run s...

Страница 13: ...wire input A3 PPOT Provides a positive to supply accelerator s potentiometer protected against short to B and B A4 TILLER Tiller seat microswitch input active high B A5 BELLY Belly switch input used f...

Страница 14: ...ected against shortcircuit A15 PMC Line contactor coil positive supply 1 0A continuous A16 KEY Controller supply must be connected to B through a cable and a 6 3A fuse PIN REFERENCE B1 B2 NCLRXD B3 PC...

Страница 15: ...Page 14 3 6 MECHANICAL DRAWING DIMENSIONS...

Страница 16: ...ade using the Digital Console The Console is connected to the B connector of the SEM X Chopper Pay attention to the polarity of the Console Connector when connecting to the chopper The bevel on the co...

Страница 17: ...Page 16 4 3 DESCRIPTION OF STANDARD CONSOLE MENU...

Страница 18: ...Page 17 5 SEM X CABLING AND CONFIGURATION 5 1 POWER DIAGRAM...

Страница 19: ...2 5 PRESENT A11 output drives an electromechanical brake The controller does not carry out monitor function but locks the brake while in rest or alarm status 4 BATTERY CHECK ON alarm indication speed...

Страница 20: ...f the menu appears on the Display 8 Press either ROLL UP or ROLL DOWN to bring up the next the Option 9 A new Option appears on the Display 10 When the desired Option is displayed press PARAM Top Righ...

Страница 21: ...irst speed reduction active when H S is active 6 CUTBACK SPEED 2 Second speed reduction active when DIGITAL INPUT2 is active 7 MAX SPEED FORW Maximum Forward Speed obtained by weakening the Field Curr...

Страница 22: ...Nominal Field Current 15 CREEP SPEED Minimum Speed This Parameter sets the minimum voltage applied to the motor at the start of travel 16 FIELD CURR MAX Maximum field current The chopper reaches this...

Страница 23: ...92 84 77 70 63 56 48 42 38 MAX SP BACK FINE FCN 0 1 2 3 4 5 6 7 8 9 TRACTION I MAX IMax 72 76 79 81 84 86 90 94 96 100 ARMA CUR NOM ACN IMax 29 31 34 36 39 41 44 46 49 51 WEAK DROP OUT ACN 30 35 40 45...

Страница 24: ...he names of the Parameters appear on the Display 8 When the desired Parameter appears the Display will show a Level Number that will be between 0 and 9 press either PARAM Top Right or SET Bottom Right...

Страница 25: ...tester menu 2 SET FLD CURRENT Field current maximum value used to calibrate field current displayed in tester menu 3 ADJUSTMENT 01 Adjustment of the 90 threshold of the battery discharge table 4 ADJUS...

Страница 26: ...5 7 MENU ADJUSMENT 1 ADJUST BATTERY Sets the correct battery voltage level 2 THROTTLE 0 ZONE Sets the pedal curve type 3 THROTTLE X POINT Sets the pedal curve type 4 THROTTLE Y POINT Sets the pedal cu...

Страница 27: ...Page 26 5 8 SEM X TRACTION STANDARD WIRING DIAGRAMS...

Страница 28: ...er 5 5 6 Set the Acceleration Delay requirements for the machine Test the parameters in both directions 7 Set the CREEP level starting from level 0 The machine should just move when the accelerator mi...

Страница 29: ...K 5 NO FIELD CURR Field wiring not OK or field current sensor not OK 5 FW HIGH FIELD CUR Field wiring not OK or field current sensor not OK in FWD direction 5 BW HIGH FIELD CURR Field wiring not OK or...

Страница 30: ...or failed b Error in the starting sequence from the operator c Error in the wiring 5 FORW BACK AL 80 MDI This check is made continually The alarm is generated when forward and reverse direction are re...

Страница 31: ...fault is detected NPOT or PPOT are open circuit 11 FWD HIGH FIELD CURR AL 90 MDI BWD HIGH FIELD CURR AL 91 MDI NO FIELD CURR AL 58 MDI Problem detected with the field winding current Possible causes a...

Страница 32: ...ase in temperature At 90 C the chopper totally stops If the temperature of the chopper is 10 C this Alarm is also generated and the current is reduced by 80 If this alarm is displayed when the chopper...

Страница 33: ...7 FORWARD SWITCH the level of the Forward direction digital entry MA pin B6 ON VB active entry of closed switch OFF GND non active entry of open switch 8 BACKWARD SWITCH the level of the Reverse direc...

Страница 34: ...to the TESTER function 7 The first variable to be tested is shown on the Display 8 Press either ROLL UP or ROLL DOWN buttons until your desired variable for measurement appears on the Display 9 Next v...

Страница 35: ...showing how to use the SAVE function of the Digital Console 1 Opening Zapi Display 2 Press ENTER to go into the General menu 3 The Display will show 4 Press either ROLL UP or ROLL DOWN button until S...

Страница 36: ...he Digital Console 1 Opening Zapi Display 2 Press ENTER to go into the General menu 3 The Display will show 4 Press either ROLL UP or ROLL DOWN button until RESTORE PARAM appears on the display 5 The...

Страница 37: ...ening Zapi Display 2 Press ENTER to go into the General menu 3 The Display will show 4 Press ROLL UP or ROLL DOWN button until PARAMETER CHANGE appears on the display 5 The Display will show 6 Press E...

Страница 38: ...on until PROGRAM VACC appears on the display 5 The Display will show 6 Press ENTER to go into the PROGRAM VACC routine 7 The Display will show the minimum and maximum values of potentiometer wiper out...

Страница 39: ...X Part Number Description C16519 Protected 150A Fuse C16503 Protected 200A Fuse C16520 6 3A 5x20mm Control Circuit Fuse C12404 16 Way Molex Minifit Connector C12777 Insert for Molex Minifit Connectors...

Страница 40: ...level Check every 3 months Check the mechanical operation of the Contactor s Moving contacts should be free to move without restriction Check every 3 months Checks should be carried out by qualified p...

Отзывы: