Operating Manual MVisio Industrial HMI Lite
Supported bus systems
Ethernet / protocols
PROFINET (Controller/Master)
EtherNET/IP (Scanner/Master)
Modbus TCP (Master/Slave)
Field bus
Modbus RTU (Master/Slave)
CANopen (Master)
Serial
2x RS232, 2x RS422/RS485, 2x CAN
PLC data
Programming
CODESYS V3
Approved for CODESYS version
V 3.5.12.10
Programming languages
IEC 61131-3 (AWL, KOP, FUP, AS, ST)
Programming interface
Ethernet
Program memory
20000 kByte
Remanent memory
64 kByte
Other
Real time clock
Yes (battery-backed)
Accuracy of the real time clock (at 25°C)
< 100 ppm
Weight
0.9 kg
Input fuses
Electrical
Note!
For applications supposed to meet EN 61131-2 specifications and especially
voltage drops of 10 ms, the minimum voltage of the power supply is DC 18 V.