The assembly of the MVisio HMI Lite is shown in figure 2. Avoid permanent exposure to
direct sunlight to prevent the device from overheating.
The MVisio HMI Lite is not designed for the installation with corrosive chemical com-
pounds. Please check the resistance of the front foil against such compounds before the
assembly.
Note!
Do not use tools (e.g. screw drivers) to operate the touch screen of the
panel.
In order to meet the requirements of the protection class, the HMI Lite must be mounted
properly. The following directions must be observed during this process:
The brinks of the cut-out must be flat.
Tighten the bolts until the frame corners are in contact with the HMI Lite (see fig. 3).
The wall cut-out for the HMI Lite must be in accordance to the dimensions given in this
operating manual.
The IP66 protection class of the display can only be guaranteed, if
-
the gap between the HMI Lite and mounting wall is ≤ 0.5 mm.
-
the thickness of the mounting wall is between 1.5 and 6 mm.
-
the maximum surface roughness of the mounting wall in the region of the sealing
is ≤ 120 μm
Install the mounting in the following way:
Figure 3: Usage of the assembly clamps