Install-Xander_Insert_BUILT-IN_ZC - 2021-11-25.docx www.yunca.co.nz
Page 4 of 18
G.
Xander Wood Burner Dimensions
(Fig. 1)
Dimensions given include the Built-in
“Zero Clearance” cabinet and also
the bottom infill fascia panel, which
is required for ZC installations.
Vented fascia top panel must be
used for Built-in (ZC) installations.
(The blank fascia top panel is for masonry installations
only)
H.
Cavity Dimensions
H1.
Cavity should be prepared based on the
given minimum clearances or greater.
(Table 1) & (Fig. 2)
Increasing the cavity dimensions slightly
will make installation easier.
Non-combustible material must be used
on front wall between appliance and first
nogging/frame of enclosure.
Heat-sensitive structures not to contact
carcass or appliance fascia.
Ensure wiring for fan
(Fig. 11)
is taken into
account when preparing cavity.
WARNING:
Cavity Dimensions must be determined in conjunction with requirements as per Section E
and Section L, with particular note made to the heat sensitive material exclusion zone.
I.
Cavity Venting
I1.
A 10,000mm² vent must be installed at least 600mm up from the base of the
enclosure. This can be any configuration as long as it equates to at least 10,000mm².
[For example: 1 hole at 100 x 100mm, 2 holes at 100 x 50mm, or 4 holes at 50 x 50mm].
I2.
Suitable precautions should be taken to prevent rodents, birds and/or debris from
entering or obscuring the air vents. If grilles are used; ensure the minimum vent area
is maintained through the grille.
Table 1
BUILT-IN (ZC) CAVITY
MINIMUM DIMENSIONS (mm)
WIDTH
(W)
HEIGHT
(H)
DEPTH
(D)
790
731
555
Min timber cavity framing height 1315mm
Fig. 1
Fig. 2
(Not to scale)