Install-Xander_Insert_BUILT-IN_ZC - 2021-11-25.docx www.yunca.co.nz
Page 3 of 18
A.
Yunca recommends that competent trades persons carry out all installations (e.g. a
NZHHA Registered Installer), to obtain maximum performance and safe, efficient
heating.
B.
A consent is required and we suggest you check with local building inspectors as by-laws
do vary from area to area. Also notify your Insurance Company that a solid fuel heater
has been installed.
C.
Floor Protector
C1.
Built-in (ZC) installations: Floor protector (Promina/Bellis Board or similar non-
combustible material) must be installed so that its leading edge is a minimum of
500mm in front of the appliance base [with fascia attached].
The floor protector
must be a minimum of 860mm wide x 1090mm deep x 9mm thick.
C2.
Front floor protector clearances may be reduced if appliance is elevated.
(Table 2)
D.
Seismic restraint.
D1.
Heater must be restrained from seismic movement
(Fig. 9)
as required by AS/NZS
2918:2001
E.
Heat sensitive materials exclusion zone.
E1.
Non-combustible front cladding
must be used
, to a minimum of 600mm above the
top-most panel vent, and a minimum of 30mm either side of the fascia (152mm
either side of the outer casing of the firebox (Zero Clearance Kit).
(Fig. 5)
E2.
No heat-sensitive material is permitted to contact the fascia forming or surrounding
the front of the installation.
E3.
No heat-sensitive material is to be placed any closer than 1315mm from the base of
the Zero Clearance Box, 20mm from either side, or 20mm from the rear.
E4.
Where a nogging or lintel is required, a steel angle or other suitable non-combustible
alternative should be used if within the aforementioned exclusion zone.
F.
Mantel Clearances.
F1.
Built-in Zero Clearance installation must have a minimum of 1300mm from the
underside of the mantel shelf to the top of the appliance hearth. The mantel shelf
must not protrude further than 250mm into the room. Minimum clearance of
1200mm from the underside of the mantel key (first combustible above appliance) to
the top of the appliance hearth. The mantel key must not protrude further than
30mm into the room.
F2.
All installations must have a minimum of 600mm vertically from the top vent to the
nearest combustible material.
F3.
A 100mm heat deflector
must be installed directly above the fascia for the full width
of the appliance if a combustible mantel key or shelf is present.
F4.
Mantel uprights must not protrude further than 70mm into the room, and be no
closer than 30mm to the fascia on the side of the appliance where fans are
(internally) hard wired. For units with external wiring using the included cable
through the side panel, the side clearance to mantel uprights should be a minimum
of 100mm to allow for the cable exiting the side panel.