1.4  Rear Terminal Layout and Wiring 

Wiring diagram at back side 

1:  For  linear  voltage  input,  if  the  range  is 

below 500mV, connect to terminals 19 and 

18.    0

5V  or  1

5V  signal  can  be  input 

from terminals 17 and 18. 

2: 4

20mA signal can be converted to 1

5V signal by a 250 ohm resistor and input 

from terminals 17 and 18. If I4 module is 

installed in MIO slot, 4

20mA signal can 

be input from terminals 14+ and 15- and 

2-wire transmitter can be input from 

terminals 16+ and 14-. 

3:  The  compensation  wires  for  different 

kinds  of  thermocouple  are  different,  and 

should be directly connect to the terminals.   

When  the  internal  auto  compensation 

mode  is  used, connecting  the  common  wire  between  the  compensation  wire  and the terminals  will  cause  measurement 

error. 

4: Main output from terminals 13+ 11- as current output, single channel SSR voltage output. 

 

 

Wiring diagram of D size instruments (72×72mm) 

1:  Linear  voltage  signal  of  range  below  500mV  input  from 

terminals 13 and 12. 0

5V and 1

5V input from terminals 11 

and 12. 

2:  4

20mA  linear  current  signal  can  be  converted  to  1

5V 

voltage signal by connecting a 250 ohm resistor and input from 

terminals 11 and 12. 

3:  S,  S1  or  S4  module  can  be  installed  in  COMM  slot  for 

communication.    If  relay,  TRIAC  no  contact  switch,  or  SSR 

driver  voltage  output  module  is  installed  in  COMM,  it  can  be 

used  as  AL1  alarm  output.  If  I2  module  is  installed  in  COMM 

and  parameter  “bAud”  set  to  1,  then  on-off  signal  in  MIO  is  simulated.  Setpoints  SV1  and  SV2  can  be  switched  by 

connecting an external mechanical switch at terminals 3 and 4. 

 

 

Note:  This  graph  is  for  upright 
instruments with dimension A, C 
or E. 

For instruments with dimension 
B  and  F,  just  clockwise  rotate 
the  graph  90  degree  and  the 
terminal  numbers  keep  the 
same. 

AU1

 

M2/MIO 

AUX 

ALM 

COMM 

AL2

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

11

 

12

 

15

 

16

 

17

 

18

 

19

 

20

 

13

 

14

 

AL1   

 

AU2

 

COM

 

 

COM 

 

N/O 

 

 

N/C 

 

 

N/O 

 

 

N/O 

 

 

+

 

+

 

A

 

B

 

+

 

100-240VAC~

 

+

 

+

 

OUTP 

COM

 

 

COM 

 

N/O 

 

 

N/C 

 

N/O 

 

 

N/O 

 

 

COM

 

 

COM 

 

N/O 

 

 

N/O 

 

 

N/O 

 

 

N/C 

 

 

+

 

+

 

OP2

 

OP1

 

+

 

0-5V 
1-5V

 

G1 

 

 

G2 

 

 

G1 

 

 

G2 

 

 

G1 

 

 

G2 

 

 

Thyristor trigger output

K1/K3

 

 

 

Thyristor trigger output

K3

 

 

 

Thyristor trigger output

K3

 

 

 

+

 

COM 

 

N/C 

 

 

V+ 

 

 

N/O 

 

 

+

 

+

 

+

 

RXD

 

GND

 

TXD

 

 

 

AU1

 

AUX 

COMM/AL1 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

11

 

12

 

13

 

14

 

10

 

AU2

 

COM

 

 

COM 

 

N/O 

 

 

N/C 

 

 

N/O 

 

 

N/O 

 

 

+

 

+

 

A

 

B

 

+

 

100-240VAC~

 

+

 

+

 

OUTP 

COM

 

 

COM 

 

N/O 

 

 

N/C 

 

N/O 

 

 

N/O 

 

 

OP2

 

OP1

 

+

 

0-5V 
1-5V

 

G1 

 

 

G2 

 

 

Thyristor trigger output

K1

 

 

 

COM 

 

N/O 

 

 

+

 

TXD

 

RXD

 

GND

 

Содержание AI-519

Страница 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Страница 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Страница 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Страница 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Страница 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Страница 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Страница 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Страница 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Страница 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Страница 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Страница 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Страница 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Страница 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Страница 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Страница 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Страница 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Страница 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Отзывы: