background image

 

 

12 

displaying output magnitude, the output magnitude can be modified by pressing 

  or 

 

. By setting M-A parameter, 

the instrument can be locked at automatic or manual control mode to avoid entering manual operation by mistake. 

Auto Tuning (AT) 

When artificial intelligence PID control or standard PID control is chosen (CtrL=APId or nPId),    the PID parameters can 

be  obtained  by  running  auto-tuning.    In  basic  display  status,  press 

 

 

for 2 seconds, the “At” parameter will appear.   

Press 

 

  to change 

the value of “At” from “oFF” to “on”, then press 

  to active the auto-tuning process.    During 

auto tuning, “At” will flash at lower display window and the instrument executes on-off control.    After 2 cycles of on-off 

action,  the  instrument  will  obtain  the  values  of  PID  control  parameters.    If  you  want  to  escape  from  auto  tuning  status, 

press and hold 

 

 

for about 2 seconds until the "At" parameter appears again.    Change “At” from “on” to “oFF”, press 

  to  confirm,  then  the  auto  tuning  process  will  be  cancelled.    After  satisfying  PID  parameters  are  obtained,  At  is 

recommended to be “FoFF” which prevents activating auto tuning in basic display status.   

Note 1: 

The advanced artificial intelligence algorithm  is able to avoid overshooting problem of standard PID algorithm 

and achieve precise control.   

 

Note 2: 

If the setpoint is different, the parameters obtained from auto-

tuning are possibly different.    So you’d better set 

setpoint  to  an  often-used  value  or  middle  value  first,  and  then  start  auto-tuning.    For  the  ovens  with  good  heat 

preservation,  the  setpoint  can  be  set  to  the  highest  applicable  temperature.    It  is  forbidden  to  change  SV  during  auto 

tuning.    Depending on the system, the auto-tuning time can be from several seconds to several hours. 

Note 3: 

Parameter  CHYS  (on-off  differential,  control  hysteresis)  has  influence  on  the  accuracy  of  auto-tuning.     

Generally, the smaller the value of CHYS, the higher  is the precision of auto tuning.    But the value of CHYS parameter 

should be large enough to prevent the instrument from error action around setpoint due to the oscillation of input.    CHYS 

is recommended to be 2.0. 

Note 4: 

AI  series  instrument  has  the  function  of  self-adaptation.    It  is  able  to  learn  the  process  while  working.    The 

control effect  at  the  first  run after  auto  tuning  is  probably  not  perfect,  but  excellent  control  result  will  be  obtained  after  a 

period of time because of self-adaptation. 

3. PARAMETERS AND SETTINGS 

3.1 

Parameter Lock (Loc) and Field Parameters 

In order to protect important parameters from being modified by mistake but also offer enough flexibility for field control, 

parameter lock (Loc) and field parameters are introduced.   

The  parameters  need  to  be  displayed  and  modified  in  the  work  field  are  called  Field  Parameters.    The  set  of  field 

parameters is a subset of the whole parameter set, and can be freely chosen by user.   

Loc can authorize different security right as below: 

Loc=0

1, allowed to modify field parameters and setpoint, and execute auto tuning; 

Loc=2, a

llowed to modify field parameters, but can’t modify setpoint. 

Loc=3

255: can only modify “Loc” 

Setting Loc=PASd (Password, a number between 256 and 9999.  Default is 808) and then pressing 

  to confirm will 

enter the complete parameter table and modify all parameters. 

1 to 8 field parameters can be defined by parameters EP1 to EP8.    If the number of the field parameters is less than 8, 

the first idle EP parameter should be set to “nonE”.     

Parameters 

EP1 

EP2 

EP3 

EP4 

EP5 

EP6 

EP7 

EP8 

Loc 

Default Value 

HIAL 

LoAL 

HdAL 

LdAL 

nonE 

nonE 

nonE 

nonE 

You can redefine field parameters and Loc to change operation style. For example, you can execute auto tuning from field 

parameter instead of by pressing 

 

  in basic display status, and only take HIAL and HdAL as field parameter.   

Parameters 

EP1 

EP2 

EP3 

EP4 

EP5 

EP6 

EP7 

EP8 

Loc 

At 

Default Value 

HIAL 

HdAL 

At 

nonE 

nonE 

nonE 

nonE 

nonE 

FoFF 

 

Содержание AI-519

Страница 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Страница 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Страница 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Страница 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Страница 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Страница 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Страница 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Страница 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Страница 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Страница 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Страница 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Страница 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Страница 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Страница 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Страница 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Страница 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Страница 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Отзывы: