9
Wiring diagram of E7 size instruments (22.5 x 100mm)
1:
Input
0~5V/1~5V input from 12+, 11-
500mV below input from 10+, 11-
4~20mA with 250ohm shunt resistor converted to 1~5V, input from 12+, 11-
2: Fixed with one channel alarm and communication
3: Main output can be selected among G, X3, L2, K1, K5, K6 or W1. Alarm is
mandatorily defined as AU1
Thyristor trigger output wiring diagram (applicable for K1, K3, K5 or K6 module)
Load
Thyristor trigger output
100~240VAC
IN4001
1N4001
Load
Thyristor trigger output
SCR X2
5~500A
BX
BX
Capacitor Resistor
Absorber Circuit
Varistor
G1
G2
G1
G2
ZNR
ZNR
V
V
100~240VAC
TRIAC
5~500A
Capacitor Resistor
Absorber Circuit
Varistor
SCR Power Module
1: According to the voltage and current of load, choose suitable varistor to prevent the thyristor. Capacitor resistor
absorber is needed for inductance load or phase-shift trigger output.
2: SCR power module is recommended. A power module includes two SCRs, is similar to the above dashed square.
3: K5 phase-shift trigger module is only suitable for 200
~
240VAC / 50Hz power. K6 phase-shift trigger module is only for
380VAC below non-standard environment.