Additional Notes 

Decimal Places 

When the measuring value and all parameter value shows 0.1

 or 0.1

 during measuring temperature (depends on 

parameter setting Fru), the range of parameter will become 

–999.0

+3000.0

 or 

–999.0

+3000.0

, even the 

default range is-9990

+30000. The decimal place after 999.9 will be truncated. For linear signal definition, the decimal 

place are only for display. The value showing does not affect internal resolution and scale. 

 

 

Alarm blocking at the beginning of power on 

Some unnecessary alarms often occur at the beginning of power on. In a heating system, at the beginning of powers on, 

its  temperature is much lower  than  the  setpoint.    If  low  limit  and  deviation  low  limit are set  and  the  alarm  condition  are 

satisfied, the instrument should alarm, but there is no problem in the system.    Contrarily, in an refrigerating system, the 

unnecessary high limit or deviation high limit alarm may occur at the beginning of power on.    Therefore, AI  instruments 

offer the function of alarm blocking at the beginning of power on.    When Act is set to rEbA or drbA, the corresponding low 

or  high  alarms  are  blocked  until  the  alarm  condition  first  clears.    If  the  alarm  condition  is  satisfied  again,  the  alarm  will 

work. 

 

Temperature Transmitter 

Besides  AI  PID,  stand  PID  control  and  on-off  control,  if  the  output  is  defined  as  current  output,  the  instrument  can  also 

retransmit  PV  (process  value)  into  linear  current.  The  precision  of  current  output  is  0.2%FS,  as  0.5%FS  transmitter 

counted whole system.   

Parameter setting suggestion 

CtrL=POP 

InP=0 

SCL=0.0 

SCH=400.0 

Opt=4-20 

The input reads from a K thermocouple, ranging 0

400

, output current as 4

20mA. 

Содержание AI-519

Страница 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Страница 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Страница 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Страница 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Страница 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Страница 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Страница 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Страница 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Страница 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Страница 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Страница 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Страница 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Страница 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Страница 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Страница 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Страница 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Страница 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Отзывы: