JOHNSON CONTROLS

53

SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION

FORM 161.01-OM1 

ISSUE DATE: 6/8/2018

3

UPS BATTERY MONITORING

DISPLAY ONLY FIELDS

FIELD/LED NAME

DESCRIPTION

Line Low Battery Voltage Offset, 

Inverter Low Battery Voltage Thresh-

old, Line Low Battery Voltage Thresh-

old

These are control setpoints for battery health fault logic.

PROGRAMMABLE

PROGRAMMABLE

BUTTON

ACCESS LEVEL

DESCRIPTION

Start Battery 

Test

Operator

Initiates a battery load test. Only applies when chiller is shutdown and manual 
operation of power supply to the chiller can be performed.

NAVIGATION

NAVIGATION

BUTTON

DESCRIPTION

Home

Returns user to HOME Screen

Compressor

Causes an instant return to the Compressor Screen.

VSD

Causes an instant return to the Variable Speed Drive Screen.

Содержание YZ MODEL A

Страница 1: ...GNETIC BEARING CENTRIFUGAL CHILLER WITH OPTIVIEW CONTROL CENTER CENTRIFUGAL LIQUID CHILLERS WITH R 1233zd REFRIGERANT OPERATIONS AND MAINTENANCE NEW RELEASE Form 161 01 OM1 618 Issue Date June 8 2018...

Страница 2: ...his document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in ques...

Страница 3: ...ld verify whether the equipment has been modified and if current litera ture is available from the owner of the equipment prior to performing any work on the chiller CHANGE BARS Revisions made to this...

Страница 4: ...A Product Family Stage End Name Motor End Name Special Contract VSD Name Unit Mod Level YZ MA033 AN030 P042N A Voltage VSD Family Frequency VSD Output Amp Code P 042 N A C A 6 6 Impeller Configuration...

Страница 5: ...mit 2 3 Pass Evap Family Evap Diameter Inches Evap Mod Level Evap Length Feet Evap Bundle Code Evap Number of Passes Evap Waterbox Mod Level Evap Waterbox Family Evap Waterside DWP Cond Family Cond Di...

Страница 6: ...ges 29 Analog Input Ranges 29 Display Messages 90 Master Slot Numbers List For Use With Trend Feature 87 SECTION 4 VSD OPERATION 107 PYT Model VSD Overview 107 PYT Model VSD Components 107 PYT Model V...

Страница 7: ...E DATE 6 8 2018 SECTION 6 PRINTING 129 Printing Overview 129 Downloading System Prints to a Laptop 129 SECTION 7 DECOMMISSIONING DISMANTLING AND DISPOSAL 139 Temperature 140 APPENDIX MATERIAL SAFETY D...

Страница 8: ...r Screen 68 FIGURE 27 Sales Order Screen 70 FIGURE 28 Operations Screen 72 FIGURE 29 Remote Control Screen 73 FIGURE 30 History Screen 74 FIGURE 31 History Details Screen 76 FIGURE 32 Custom Screen 77...

Страница 9: ...reshold 22 TABLE 2 Temperature Setpoint 23 TABLE 3 Input Current Limit Threshold 23 TABLE 4 Analog Input Ranges 29 TABLE 5 Status Messages 90 TABLE 6 Run Messages 91 TABLE 7 MBC Startup Messages 91 TA...

Страница 10: ...JOHNSON CONTROLS 10 FORM 161 01 OM1 ISSUE DATE 6 8 2018 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 11: ...ingement on the tubes A separate subcooler is located in the condenser to enhance performance Single or dual refrigerant relief valves are located on the condenser shell unless the optional refrigeran...

Страница 12: ...FUNDAMENTALS LD22373 Suction Line Magnetic Bearing Motor Purge Compact Waterboxes Evaporator Figure 1 YZ CHILLER COMPONENTS REAR LD22514 Variable Speed Drive Optiview Control Panel Liquid Level Senso...

Страница 13: ...pad is the interface for starting stop ping configuring monitoring and commanding the chiller The control center is a microprocessor based system designed for centrifugal chillers It controls the LCHL...

Страница 14: ...on Remote Ready to Start Contacts Safety Shutdown Contacts Cycling Shutdown Contacts The OptiView panel can be used to control the cus tomer chilled and condenser liquid flow A set of con tacts exists...

Страница 15: ...ime the unit is in operation The speed at which the compressor rotates establishes the pressure differential that the chiller can operate against This is referred to as lift Speed must always be maint...

Страница 16: ...while the chiller is running An excess surge condition is detected by comparing the number of surge events that occur in a selectable time period to a selectable threshold If the number of surge even...

Страница 17: ...1 7 C to 16 7 C 3 F to 30 F Water Quality Water quality may affect the performance of any chill er through corrosion deposition of heat resistant scale sedimentation or organic growth These will degr...

Страница 18: ...that the chilled water pump is protected by the strainer The strainer is important to protect the chiller from debris or objects which could block flow through individu al heat exchanger tubes A reduc...

Страница 19: ...IGERANT STATES High Pressure Vapor Low Pressure Vapor High Pressure Liquid Refrigerant Low Pressure Liquid Refrigerant 1 Compressor 2 Optional Hot Gas By pass Valve 3 Suction Line 4 Evaporator 5 Falli...

Страница 20: ...JOHNSON CONTROLS 20 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 1 SYSTEM FUNDAMENTALS THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 21: ...perature inside any JCI supplied liquid cooled motor starter must be maintained above the dewpoint tem perature in the equipment room to prevent condensing water vapor inside the starter cabinet An ad...

Страница 22: ...eaving the evaporator must be set by the operator The way it is selected depends on whether the operator wants this value set locally or modulated by a remote input Regardless of which method is used...

Страница 23: ...wire The Remote Setpoint Minimum is user selectable at the Operator password level between 0 0 F and 200 0 F 17 8 C and 93 3 C default 0 0 F 17 8 C The Remote Setpoint Maximum is also user selectable...

Страница 24: ...st be pressed before the chiller will again permit a start via the remote source 3 In an emergency situation requiring immediate stoppage a safety stop switch is located on the side of the control pan...

Страница 25: ...st all system joints for refrigerant leaks with a leak detector If any leaks are found they should be re paired before allowing the system to stand for a long period of time 2 During long idle periods...

Страница 26: ...JOHNSON CONTROLS 26 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 2 SYSTEM OPERATING PROCEDURES THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 27: ...efaults to the lowest access level which is termed VIEW In this mode the chiller operating values and setpoints can be ob served but no changes can be made OPERATOR The second access level is termed O...

Страница 28: ...signed to enable the cursor arrow keys below the numeric keypad which are used to high light the desired setpoint field At this point the key is pressed to bring up a dialog prompting the user to ente...

Страница 29: ...the or symbols will be displayed beside the mini mum or maximum value respectively Table 4 ANALOG INPUT RANGES ANALOG INPUT ENGLISH RANGE METRIC RANGE LOW HIGH UNITS LOW HIGH UNITS Leaving Chilled Liq...

Страница 30: ...percentage of full load amps utilized by the system Input Power kW This displays the total input power used by the system Operating Hours Displays the cumulative operating hours of the chiller Motor...

Страница 31: ...ter causes the chiller to start if control source is LOCAL or permits run if the Run Stop source is any remote mode Soft Stop OPERATOR This key is displayed whenever the chiller is running It shows in...

Страница 32: ...f the liquid as it enters the condenser Condenser Liquid Temperature Leav ing Displays the temperature of the liquid as it leaves the condenser Chilled Liquid Temperature Entering Displays the tempera...

Страница 33: ...temperature in the evaporator calculated from evaporator pressure Isolation Valves LEDs Only show when optional brine isolation valve feature exists and enabled Closing The control is commanding the...

Страница 34: ...re Setpoints Setpoint Displays the present setpoint to which the chiller is operating whether controlled locally or remotely Leaving Chilled Liquid Temperature Setpoints Shutdown Displays the Leaving...

Страница 35: ...PROGRAMMABLE BUTTON ACCESS LEVEL DESCRIPTION Local Leaving Chilled Liquid Temperature Setpoint Operator This value allows the user to define the Leaving Chilled Liquid Temperature that is to be maint...

Страница 36: ...isplays the temperature of the refrigerant in the drop leg between the condens er and evaporator shells Subcooling Temperature Displays the difference between the Condenser Refrigerant temperature and...

Страница 37: ...ays the position command to the level control valve in percent of travel with 0 full closed to 100 full open NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Home Screen P...

Страница 38: ...closed indicating that the Purge Tank is full of refrigerant Purge Compressor Run LED Indicates ON when the Purge Compressor runs Purge Suction Temperature Displays the Purge Compressor Suction Tempe...

Страница 39: ...7 F 21 7 C a purge cycle will be initiated Purge Mode Enhanced Operator Purge Inlet Solenoid is Open and the Purge Pump Solenoid is Closed When the chiller runs if the Condenser Saturation Temperature...

Страница 40: ...ntage of the job input Full Load Amps FLA value Motor Full Load Amps Displays the current to the motor as a percentage of the motor maximum cur rent VSD Output Frequency Displays the VSD frequency NAV...

Страница 41: ...that allows viewing and programming of the Surge Protection feature VGD Moves to the subscreen that allows viewing and calibrating the Variable Geom etry Diffuser feature Programming requires an acce...

Страница 42: ...m the highest of the three phase Input Currents Input Job FLA setting 0 9 Input Current FLA Override Thresh old Displays the active input current percent limit which is the minimum of Local Input Curr...

Страница 43: ...erride is in control Condenser Pressure Condenser Pressure Override is in control Evaporator Pressure Evaporator Pressure Override is in control Low LCHLT LCHLT low temperature Override is in control...

Страница 44: ...ON 3 OPTIVIEW CONTROL CENTER FUNCTIONS AND NAVIGATION NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes and instant return to the Home Screen Compressor Causes an instant navigation to the Compress...

Страница 45: ...plays the K Bearing Temperature in F or C H1 Bearing Temperature Displays the H1 Thrust Bearing Temperature in F or C H2 Bearing Temperature Displays the H2 Thrust Bearing Temperature in F or C Avg Po...

Страница 46: ...Average Force of the Radial Bearing J in the X and Y axis Thrust Bearing H and the Radial Bearing K in the X and Y axis Expressed in lbs or Nm J1 J2 J3 J4 Current Displays the four magnetizing curren...

Страница 47: ...t Displays the number of surge events that have occurred in the last 1 to 5 min utes as programmed with the COUNT WINDOW setpoint If the chiller has been running for less than the COUNT WINDOW minutes...

Страница 48: ...default 5 default 3 in which the number of surge events SURGE WINDOW COUNT are compared to the maximum allowed COUNT LIMIT for the purpose of detecting an excess surge situation Count Limit Operator A...

Страница 49: ...of the VGD over the range of 0 fully closed to 100 fully open Displayed as XXX until calibration procedure is performed by a qualified Service technician VGD Command Displays the position command fro...

Страница 50: ...of the 3 sensors at either end of the motor to be disabled When an individual temperature is disabled the temperature data box does not appear Any input that registers as open will display the minimu...

Страница 51: ...e optional Ambient Dew Point Temperature sensor is Enabled its read ing is displayed here Motor Cooling Valve Command Output to the motor cooling valve in percent from 0 closed to 100 Opened Motor Coo...

Страница 52: ...r to supply loads and any necessary current to the power storage battery UPS Inverter LED Indicates the UPS is providing power from the storage battery UPS Fault LED Indicates the UPS has faulted UPS...

Страница 53: ...sh old These are control setpoints for battery health fault logic PROGRAMMABLE PROGRAMMABLE BUTTON ACCESS LEVEL DESCRIPTION Start Battery Test Operator Initiates a battery load test Only applies when...

Страница 54: ...lue in use This value can come from a 4 20mA 0 10VDC or PWM signal in a Hardwired Remote mode an SC Equip or interface in BAS mode or a locally programmed value Pulldown Demand Time Left Displays the...

Страница 55: ...urrent reaches this value the input current override takes effect Pulldown Demand Limit Operator Allows the user to specify the current limit value as a percentage of FLA to which the chiller will be...

Страница 56: ...Amps Input Current Displays the Input Current to the VSD Motor Full Load Amps Displays the rated motor FLA VSD Model Displays the VSD model as reported by the VSD Water Pump Output LED Indicates the...

Страница 57: ...3 OPTIVIEW CONTROL CENTER FUNCTIONS AND NAVIGATION FORM 161 01 OM1 ISSUE DATE 6 8 2018 3 NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Home screen VSD Causes an instan...

Страница 58: ...rating Mode Displays Run or Stop Phase Rotation Displays rotation sequence of the incoming power DC Bus Voltage Displays the DC Bus voltage for the harmonic filter Total Supply kVA Displays the supply...

Страница 59: ...3 OPTIVIEW CONTROL CENTER FUNCTIONS AND NAVIGATION FORM 161 01 OM1 ISSUE DATE 6 8 2018 3 NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Home screen VSD Causes an instan...

Страница 60: ...erature Leaving Chilled Liquid Temperature Cycling Shutdown Offset This Offset is the number of degrees below the Setpoint that the chiller will shut down on Low Leaving Chilled Water Temp Leaving Chi...

Страница 61: ...ich the pulldown demand limit will be in effect after the chiller starts Local Cooling Setpoint Operator This value allows the user to define the Leaving Chilled Liquid Temperature that is to be maint...

Страница 62: ...Displays what mode of operation the chilled liquid pump contacts have been configured to operate Standard or Enhanced Enhanced Pump contacts open at the completion of system coastdown except when the...

Страница 63: ...prompted for the information again At this point the user may retry the time entry or cancel the programming attempt 12 24 Hr Operator Allows the user to specify the format in which the time will be...

Страница 64: ...a given day can be cancelled by setting both the Start time and Stop time to 12 00 AM If the Start time equals the Stop time with any time other than 12 00 AM the chiller is OFF for that day If the us...

Страница 65: ...the present week As each week goes by the new schedule will be created for the present week using the Excep tion specification in combination with the Standard week def inition as described above Sel...

Страница 66: ...ish French German Hungarian Italian Japanese Portuguese Simplified Chinese Spanish Korean Russian Turkish and Traditional Chinese English Metric Units Operator Define the unit system English or Metric...

Страница 67: ...alog box is displayed permitting data entry Printer Baud Rate Operator Define the baud rate at which the panel shall communicate to the printer Printer Data Bit s Operator Define the number of data bi...

Страница 68: ...urring at the interval defined above Log Start Time Operator Set the time at which scheduled print logs will begin Output Interval Operator Define the interval at which log printing will occur Printer...

Страница 69: ...ION 3 OPTIVIEW CONTROL CENTER FUNCTIONS AND NAVIGATION FORM 161 01 OM1 ISSUE DATE 6 8 2018 3 NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Home Screen Setup Return to t...

Страница 70: ...f passes Evaporator and Condenser Water Box Press Factory defined Water Box Pressure rating Evaporator and Condenser Pressure Drop Factory defined Pressure drop across the shell Evap and Cond Nozzle A...

Страница 71: ...Inrush Amps Refrigerant Factory defined type of Refrigerant Capacity Factory defined chiller Tonnage Gear Code Factory defined compressor Gear Code Liquid Type Factory defined Liquid Type Water or Br...

Страница 72: ...Time Displays the amount of time the chiller has been running since the last start signal was received Value is reset to zero when the chiller enters Coastdown It remains at zero while shutdown and du...

Страница 73: ...the user may then choose the source for Current Limit Setpoint of the chiller Local BAS 0 10V 4 20mA or PWM Default Local NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the...

Страница 74: ...t 50 safety or cycling shutdowns that occur while the system is running or stopped PROGRAMMABLE PROGRAMMABLE BUTTON ACCESS LEVEL DESCRIPTION Select Fault Operator Allows the user to select which type...

Страница 75: ...rint History Operator This generates a report listing the status of the chiller parameters at the time of the selected shutdown Print All Histories Operator This generates a report listing the status...

Страница 76: ...Operator Scroll up in the displayed data if applicable Print History Operator This generates a report listing the status of the chiller parameters at the time of the selected shutdown NAVIGATION NAVI...

Страница 77: ...en History View Causes an instant return to the History Screen Setup Operator Causes a jump to the subscreen where the parameters to be displayed on the custom screen are selected This screen allows u...

Страница 78: ...available parameters Select Operator First use the Page Up and Page Down keys to scroll through the Slot Numbers list and note the number of the parameter s to be displayed Pressing the Select key pla...

Страница 79: ...OPTIVIEW CONTROL CENTER FUNCTIONS AND NAVIGATION FORM 161 01 OM1 ISSUE DATE 6 8 2018 3 NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Home Screen Custom View Causes a re...

Страница 80: ...that param eter the value will be plotted at the minimum value Similarly if the actual value is greater than the Y axis label maximum for that parameter the value will be plotted at the maximum value...

Страница 81: ...ta Select Operator Allows the user to display all trended data points simultaneously or select a single trended data point for display hiding the other data points Selections are ALL DATA or DATA POIN...

Страница 82: ...t only determines the sample interval but also the full screen time dis play The full screen time display is a result of the selected interval in seconds multiplied by the 450 data points To select th...

Страница 83: ...een with the words TREND MAX MUST BE TREND MIN If the parameter selected for this data point is a digital type on off this value must be set to zero 0 Zero indicates the OFF state Data Point Max 1 6 O...

Страница 84: ...ted as true then the data collection is started or stopped af ter any selected Trigger delay per the selected Trigger Action A Secondary Trigger can be evaluated with the Prima ry Trigger to start sto...

Страница 85: ...tart data collection will begin after the triggers evaluate as true and the delay timer has elapsed If the Trigger Action is set to Stop data collection will stop after the Triggers evaluate as true a...

Страница 86: ...erator Scroll up in the displayed data Print Operator Generates a list of the slot numbers of the available parameters NAVIGATION NAVIGATION BUTTON DESCRIPTION Home Causes an instant return to the Hom...

Страница 87: ...2056 Condenser Refrigerant Temperature COMPRESSOR 1296 Discharge Temperature 1299 Discharge Superheat 17748 Discharge Superheat Limiting Allowed 17750 Discharge Superheat Limit Threshold 18397 Adjust...

Страница 88: ...e 8707 Motor Housing Temperature Setpoint 8752 Motor Winding Temperature Setpoint 8723 Ambient Dew Point Temperature 8708 Motor Cooling Valve Command 8710 Motor Cooling Control State MBC 24032 MBC Com...

Страница 89: ...S Fault 24360 UPS Battery Voltage 24358 UPS Inverter Enable PURGE 24322 Purge Control State 24323 Purge State Timer 24324 Purge Compressor Run 24325 Purge Pump Run 24326 Enhanced State Count 24327 Tot...

Страница 90: ...is performing a Soft Shutdown Simultaneously the Hot Gas Bypass Valve is com manded to 100 open if Hot Gas Bypass is Enabled the compressor VGD commanded to close rapidly The motor drive speed is slow...

Страница 91: ...me expires Table 7 MBC STARTUP MESSAGES MESSAGE DESCRIPTION WAITING FOR FLOW The chilled liquid or condenser flow switch input is not reading voltage indicating no presence of flow from the flow switc...

Страница 92: ...DEL This warning is set when the Harmonic Filter Model is invalid The warning is rest when the filter model is valid or the filter operation is inhibited WARNING MBC SPEED SIGNAL FAULT The speed signa...

Страница 93: ...motor failed or dirty purge condenser coil WARNING PURGE HIGH COIL TEMP INHIBIT This warning is displayed when the Purge Coil Temperature is 0 F 17 8 C for 10 minutes after the purge compressor has b...

Страница 94: ...not receive a proper reply from the IEEE 519 logic board after attempting to communicate ten times in a row the Micropanel shall display the message WARNING HARMONIC FILTER DATA LOSS and X s shall be...

Страница 95: ...rol center configuration CONTROL PANEL POWER FAILURE A Control Power failure has occurred If the power failure occurred while the chiller was running it will automatically restart when power is restor...

Страница 96: ...itions are met thresholds of consecutive timeouts ID mismatches checksum failures or error packets It is released when a valid response is received MULTIUNIT CYCLING CONTACTS OPEN The Multiunit Cyclin...

Страница 97: ...n the wiring label for the drive VSD LOGIC BOARD POWER SUPPLY This shutdown is generated by the VSD logic board and it indicates that the low voltage power supplies for the logic board have dropped be...

Страница 98: ...VSD RUN SIGNAL Redundant RUN signals are generated by the control center one via TB6 24 and the second via the Serial Communications link If both run commands are not received by the VSD Logic Board...

Страница 99: ...n will be generated HARMONIC FILTER HIGH DC BUS VOLTAGE The harmonic filter logic board continuously monitors the harmonic filter DC bus volt age If the level of the DC bus voltage exceeds a range of...

Страница 100: ...he harmonic filter DC link voltage setpoint HARMONIC FILTER PHASE LOCKED LOOP This shutdown indicates a circuit called a phase locked loop on the harmonic filter logic board has lost synchronization w...

Страница 101: ...FAILURE A Control Power failure has occurred If the power failure occurred while the chiller was running it will automatically restart when power is restored This message can indicate a Cycling auto r...

Страница 102: ...e OptiView panel CLEAR FAULTS key is pressed MBC HIGH AMPLIFIER TEMPERATURE This Safety Shutdown is set if the MBC Amplifier Temperature is too high The chiller can be started when the condition is re...

Страница 103: ...he speed signal cycling fault three times in a 90 minute window The window is started when not currently in a window and a MBC Speed Sig nal cycling fault is received The MBC Fault contacts open The M...

Страница 104: ...can be started after the CLEAR FAULT key is pressed UPS BATTERY NOT CONNECTED This safety fault initiates a soft shutdown if it is set while the chiller state is Running It is set during chiller state...

Страница 105: ...S BREAKER RAT ING 1 05 INPUT CURRENT OVERLOAD TRIP LEVEL AMPS 330A 240 228 Input Job FLA 1 05 420A 400 380 Input Job FLA 1 05 780A 600 571 Input Job FLA 1 05 1020A 800 761 Input Job FLA 1 05 1280A 120...

Страница 106: ...wn indicates that the filter is not operating correctly or the input current to the drive filter system is not sinusoidal This shutdown will occur if the Total Demand Distortion TDD in any one phase e...

Страница 107: ...in each PYT model cabinet AC to DC Rectifier The AC to DC converter uses 3 Silicon Controlled Rectifiers SCR s and 3 diodes One SCR and one di ode are contained in each module Three modules are requir...

Страница 108: ...ls and power components is removed through liquid cooled heat sinks and cooling coils with fans The inhibited liquid that flows through the heatsinks and cooling coils is pumped through the system by...

Страница 109: ...resistors are mounted on the side of the filter power unit to provide a discharge path for the DC bus capacitors Transistor Module The transistor module contains a temperature sensor that provides tem...

Страница 110: ...OM1 ISSUE DATE 6 8 2018 SECTION 4 VSD OPERATION LD26706 DRIVE LOGIC BOARD FILTER LOGIC BOARD Figure 38 DRIVE CABINET DOOR PYT330 PYT420 PYT780 PYT1020 LD26707 DRIVE LOGIC BOARD FILTER LOGIC BOARD Figu...

Страница 111: ...tor H Filter Trap Assembly J Cooling Coil K Cooling Fan L 300VDC Magnetic Bearing Power Supply Rectifier Figure 40 DRIVE CABINET MODEL PYT330 LD26708 E D C B A POWER UNIT J H F G K L Inverter A Main U...

Страница 112: ...DATE 6 8 2018 SECTION 4 VSD OPERATION LD26709 A B C D E F G A Filter Inductor B Input Inductor C Circuit Breaker D Filter Supply Contactor E Filter Trap Assembly F Cooling Coil G Cooling Fan Figure 4...

Страница 113: ...1 OM1 ISSUE DATE 6 8 2018 4 LD26710 C D POWER UNIT A B E F A 300VDC Magnetic Bearing Power Supply B Main UPS C UPS Battery Behind Panel D Filter Power Unit E Cooling Coil F Cooling Fan Inverter Rectif...

Страница 114: ...8 SECTION 4 VSD OPERATION LD26716 B C E A F G POWER UNIT E Circuit Breaker F Cooling Coil G Cooling Fan Rectifier Inverter D A Filter Supply Contactor B Filter Inductor C Input Inductor D Harmonic Fil...

Страница 115: ...161 01 OM1 ISSUE DATE 6 8 2018 4 LD26717 D E A B F G C A 300VDC Magnetic Bearing Power Supply B Main UPS C Bus Capacitors D UPS Battery Behind Panel E Filter Power Unit F Cooling Coil G Cooling Fan Fi...

Страница 116: ...018 SECTION 4 VSD OPERATION LD26711 B D E F G H A C A Filter Power Unit B Filter Inductor C Filter Supply Contactor D Input Inductor E Circuit Breaker F Filter Trap Assembly G Cooling Coil H Cooling F...

Страница 117: ...FORM 161 01 OM1 ISSUE DATE 6 8 2018 4 LD26712 B C POWER UNIT A D E A 300VDC Magnetic Bearing Power Supply C Main UPS B UPS Battery Behind Panel D Cooling Coil E Cooling Fan Rectifier Inverter Figure...

Страница 118: ...JOHNSON CONTROLS 118 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 4 VSD OPERATION THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 119: ...arameters for indication of tube fouling or refrigerant loss X Check three phase voltage and current balance X Check programmable operating setpoints and safety cut outs Make sure they are correct for...

Страница 120: ...ols Annually More Often If Necessary 1 Evaporator and Condenser a Inspect and clean water strainers b Inspect and clean tubes as required c Inspect end sheet 2 Compressor Drive Motor a Measure motor w...

Страница 121: ...he evaporator and condenser tubes to thoroughly dehydrate the shells If a source of hot water is not readily avail able a portable water heater should be employed DO NOT USE STEAM A suggested method i...

Страница 122: ...0 1920 10 00 10 000 52 29 670 0 1220 6 30 6 300 40 29 720 0 0990 5 00 5 000 35 29 842 0 0390 2 00 2 000 15 29 882 0 0190 1 00 1 000 1 29 901 0 0100 0 50 500 11 29 917 0 0020 0 10 100 38 29 919 0 0010...

Страница 123: ...el off and remain at this level until all of the water in the shell is vaporized When this final vaporization has taken place the pressure and temperature will continue to drop until eventually a temp...

Страница 124: ...full container of refrigerant is connected and changing containers should be done as quickly as possible to minimize the loss of refrigerant Refrigerant may be furnished in cylinders containing eithe...

Страница 125: ...0 FA3312 SA2512 770 350 2035 925 FA3312 SA2512 869 395 2035 925 FA3314 SA3314 1177 535 3520 1600 FA3314 SA3314 1302 592 4125 1875 FA3914 CA3314 1751 796 4015 1825 FA3916 SA3916 2105 957 5665 2475 FA48...

Страница 126: ...time the cooling ca pacity decreases and the split temperature difference between water leaving the evaporator and the refriger ant temperature in the evaporator increases A gradual drop off in cooli...

Страница 127: ...n the following manner if the location is not definite all the tubes will require investigations 2 Wash off both tube heads and the ends of all tubes with water 3 With nitrogen or dry air blow out the...

Страница 128: ...t 11 0 V UPS Inverter Low Battery Voltage fault thresh old the test fails and ends If the test takes longer than 75 seconds the test fails and ends If the UPS shuts down OptiView will lose power due t...

Страница 129: ...History Figure 52 on page 132 Setpoints Figure 53 on page 133 Schedule Figure 54 on page 135 Sales Order Figure 55 on page 135 Security Log Figure 56 on page 136 Trend Figure 57 on page 137 CUSTOM Sc...

Страница 130: ...ed information and the informa tion will be recorded as a txt file When the print file has been recorded select Transfer from the toolbar and capture from the drop down menu and select Stop This will...

Страница 131: ...Port SC EQUIP COM 1 RS 232 TX DB9 2 5 4 Port 2B RX TX COM GND DSR GTX GRX COM 4B J2 8 4 2 J2 7 6 Figure 50 COMMUNICATIONS BLOCK DIAGRAM A serial cable to go from the OptiView Control Pan el to the ser...

Страница 132: ...rol Valve Command 0 0 Compressor Motor Speed 1 20 Hz Discharge Temperature 84 7 F Discharge Superheat 9 4 F Adjusted Discharge Superh 9 4 F Discharge Superheat Limit 11 1 F Discharge Superheat Limit N...

Страница 133: ...Bits 8 Bits Parity None Stop Bits 1 Bit COM 2 Setup Baud 38400 Baud Data Bits 8 Bits Parity None Stop Bits 2 Bits Evaporator Leaving Chilled Local Setpoint 42 0 F Leaving Chilled ISN Setpoint 45 0 F L...

Страница 134: ...10 0 HGBP Start Position 0 0 LCHLT Setpoint Ramp Rate 0 1 F S LCHLT Setpoint Start Offset 10 0 F Temperature Control Kp 5 0 Temperature Control Ti 25 0 Temperature Control Td 0 0 Temperature Control...

Страница 135: ...EPTION DAYS 02 APR 1999 START OFF STOP OFF 13 APR 1999 START 8 00 AM STOP 10 00 PM LD26763 YORK SALES ORDER YZ CHILLER ID 1 C 2010 JOHNSON CONTROLS MON 01 NOV 2010 9 25 18 AM ORDER INFORMATION COMMISS...

Страница 136: ...ENT SALES ORDER SETUP FINISH PANEL SETUP NO LD26765 CHILLER ID 0 c 1997 2001 YORK INTERNATIONAL CORPORATION Fri 05 Oct 2001 4 48 04 PM Log Entry 1 Evaporator Leaving Chilled Local Setpoint Date 05 Oct...

Страница 137: ...ID 163 1997 2000 YORK INTERNATIONAL CORPORATION MON 09 OCT 2000 3 33 47 PM DATA 1 LEAVING CHILLED LIQUID TEMPERATURE DATA 2 RETURN CHILLED LIQUID TEMPERATURE DATA 3 EVAPORATOR PRESSURE DATA 4 LEAVING...

Страница 138: ...JOHNSON CONTROLS 138 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 6 PRINTING THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 139: ...at exchangers from the external wa ter systems and drain that section of the system If no isolation valves are installed it may be neces sary to drain the entire system If glycol was used in the water...

Страница 140: ...10 F from Fahrenheit to Celsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 16 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capa...

Страница 141: ...JOHNSON CONTROLS 141 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018 APPENDIX MATERIAL SAFETY DATA SHEETS...

Страница 142: ...JOHNSON CONTROLS 142 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 143: ...JOHNSON CONTROLS 143 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 144: ...JOHNSON CONTROLS 144 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 145: ...JOHNSON CONTROLS 145 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 146: ...JOHNSON CONTROLS 146 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 147: ...JOHNSON CONTROLS 147 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 148: ...JOHNSON CONTROLS 148 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 149: ...JOHNSON CONTROLS 149 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 150: ...JOHNSON CONTROLS 150 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 151: ...JOHNSON CONTROLS 151 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 152: ...JOHNSON CONTROLS 152 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 153: ...JOHNSON CONTROLS 153 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...

Страница 154: ...JOHNSON CONTROLS 154 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...

Страница 155: ...Canada Company is a licensee Company Identification MANUFACTURER DISTRIBUTOR E I du Pont Canada Company P O Box 2200 Streetsville Mississauga Ontario L5M 2H3 PHONE NUMBERS Product Information 1 800 38...

Страница 156: ...th the liquid may cause frostbite Individuals with preexisting diseases of the central nervous or cardiovascular system may have increased susceptibility to the toxicity of increased exposures Carcino...

Страница 157: ...ure limit therefore stop all work and ventilate to disperse refrigerant vapors from the work area before using any open flames R 404A is not flammable in air at temperatures up to 100 deg C 212 deg F...

Страница 158: ...d ventilation especially in low or enclosed places where heavy vapors might collect Remove open flames Use self contained breathing apparatus SCBA for large spills or releases HANDLING AND STORAGE Han...

Страница 159: ...Limits PENTAFLUOROETHANE HFC 125 PEL OSHA None Established TLV ACGIH None Established AEL DuPont 1000 ppm 8 12 Hr TWA WEEL AIHA 1000 ppm 4900 mg m3 8 Hr TWA 1 1 1 TRIFLUOROETHANE HFC 143a PEL OSHA Non...

Страница 160: ...toxic and irritating Contact should be avoided Polymerization Polymerization will not occur TOXICOLOGICAL INFORMATION Animal Data The blend is untested HFC 125 Inhalation 4 hour ALC 709 000 ppm in rat...

Страница 161: ...plasia and testicular weight The no effect level for this study was 10 000 ppm Animal data show slight fetotoxicity but only at exposure levels producing other toxic effects in the adult animal Reprod...

Страница 162: ...induce transformation of mammalian cells in culture or in the whole animal Tests in animals demonstrate no developmental toxicity ECOLOGICAL INFORMATION Ecotoxicological Information Aquatic Toxicity...

Страница 163: ...Acute No Chronic No Fire No Reactivity No Pressure Yes LISTS SARA Extremely Hazardous Substance No CERCLA Hazardous Material No SARA Toxic Chemicals No Canadian Regulations WHMIS Classification CLASS...

Страница 164: ...his Material Safety Data Sheet relates only to the specific material designated herein and does not relate to use in combination with any other material or in any process Responsibility for MSDS Conti...

Страница 165: ...rds None Precautionary statements Prevention Read label before use Wash skin thoroughly after handling Wear protective gloves protective clothing eye protection and face protection Response IF SWALLOW...

Страница 166: ...ishing media No information available Protective equipment and precautions for firefighters Stay upwind of the fire Full protective equipment including self contained breathing apparatus should be use...

Страница 167: ...rations Do not eat drink or smoke while handling this product Chemical Name OSHA PEL ACGIH TLV Non hazardous substances None established None established pH 7 5 8 0 Appearance Blue Clear liquid Odor M...

Страница 168: ...r other skin breaches Ingestion Gastrointestinal distress with or without nausea vomiting and diarrhea Inhalation Upper respiratory irritation with or without cough watering of the eyes and postnasal...

Страница 169: ...CAS RQ TPQ None Section 311 and 312 Health and Physical Hazards Immediate Delayed Fire Pressure Reactivity No No No No No Section 313 Toxic Chemicals 40 CFR 372 Chemical Name CAS Number Percent by Wei...

Страница 170: ...Freedom Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2018 www johnsoncontrols com ALL RIGHTS RESERVED Form 161 01 OM1 618 Issue Da...

Отзывы: