JOHNSON CONTROLS
101
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
3
MESSAGE
DESCRIPTION
AUXILIARY SAFETY –
CONTACTS CLOSED
The Auxiliary Safety shutdown input, connected to I/O Board TB2-31 senses 115 VAC, initiating a
safety shutdown. This input is a general-purpose, user defined safety shutdown input. The chiller
can be started after the contacts open and the CLEAR FAULT key is pressed.
CONDENSER – HIGH
PRESSURE
The condenser pressure, as sensed by the Condenser Transducer, has increased to greater than
40.0 PSIA. The chiller can be started after the pressure decreases to is less than 30.0 PSIA and
the CLEAR FAULT key is pressed.
CONDENSER – HIGH
PRESSURE CONTACTS
OPEN
The contacts of the electromechanical high pressure safety device, located on the con-denser
shell, have opened because this device has detected a pressure greater than 40±5 PSIG. The
contacts will automatically close when the condenser pressure decreases to is less than 20±5
PSIG. The chiller can be started after the contacts close and the CLEAR FAULT key is pressed.
CONDENSER –
PRESSURE
TRANSDUCER OUT OF
RANGE
The Condenser Pressure Transducer is indicating a pressure that is less than 0.0 PSIA or greater
than 80.0 PSIA This is outside the normal operating range of the transducer. This is generally
indicates a defective transducer. The chiller can be started after the transducer is indicating a
pressure that is within range and the CLEAR FAULT key is pressed.
CONTROL PANEL –
LOSS OF CONTROL
VOLTAGE
The line power input signal at I/O board TB3-81 was low for 1 second continuous. This signal
is used to determine when the digital inputs are affected by a line power loss versus an actual
condition for their devices. This fault is not expected on an actual loss of microboard power from
the critical load bus, because the processor will be off before the fault delay. This message can
indicate a Cycling (auto-restart after power failure) or Safety (manual restart after power failure)
shutdown, depending upon control center configuration
CONTROL PANEL –
POWER FAILURE
A Control Power failure has occurred. If the power failure occurred while the chiller was running,
it will automatically restart when power is restored. This message can indicate a Cycling (auto-
restart after power failure) or Safety (manual restart after power failure) shutdown, depending
upon control center configuration. It indicates a cycling shutdown when displayed in orange
characters; Safety shutdown when displayed in red characters. The control center is configured
for auto-restart or manual restart after power failure by a qualified Service Technician.
EVAPORATOR – LOW
PRESSURE
The evaporator pressure, as sensed by the Evaporator Transducer, has decreased to the
shutdown threshold and caused 3 cycling shutdowns in a 90 minute period. For water cooling ap-
plications, the shutdown threshold is a fixed value. For Brine cooling applications, the shutdown
threshold varies according to the concentration of the Brine solution. The Brine shutdown thresh-
old is programmed at the YORK Factory. The chiller can be started after the evaporator pressure
increases to the restart threshold and the CLEAR FAULT key is pressed.
FLUID
SHUTDOWN (PSIA)
RESTART (PSIA)
Water Cooling
6.4 to 7.4
as programmed
+0.1>
Shutdown threshold
Brine Cooling
6.4 to 7.4
as programmed
+0.1>
Shutdown threshold
EVAPORATOR –
TRANSDUCER OR
TEMPERATURE
SENSOR
A possible defective Evaporator Pressure Transducer ir Refrigerant Temperature Sensor has
been detected. The control center converts the evaporator pressure to a Saturated Temperature
value and compares this value to the optional Evaporator Refrigerant Temperature Sensor. If the
difference between these temperatures is greater than 3.0°F (1.77 °C), continuously for 1 minute,
this shutdown is performed. This check is only performed under the following conditions:
• Chiller has been running for at least 10 minutes
• Evaporator Refrigerant temperature (RT7) is enabled
• NOT in Brine cooling mode
• Evaporator Temperature Sensor (RT7) or Evaporator Saturation Temperature is indicating a
temperature of less than 32.0 °F (0 °C).
The chiller can be started after the temperatures are within 3.0 °F (1.77 °C) of one an-other and
the CLEAR FAULT key is pressed.
TABLE 12 -
SAFETY SHUTDOWN MESSAGES
The chiller can be started after manual resets are per-
formed as detailed below.
Содержание YZ MODEL A
Страница 10: ...JOHNSON CONTROLS 10 FORM 161 01 OM1 ISSUE DATE 6 8 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...JOHNSON CONTROLS 118 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 4 VSD OPERATION THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 138: ...JOHNSON CONTROLS 138 FORM 161 01 OM1 ISSUE DATE 6 8 2018 SECTION 6 PRINTING THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 142: ...JOHNSON CONTROLS 142 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 143: ...JOHNSON CONTROLS 143 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 144: ...JOHNSON CONTROLS 144 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 145: ...JOHNSON CONTROLS 145 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 146: ...JOHNSON CONTROLS 146 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 147: ...JOHNSON CONTROLS 147 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 148: ...JOHNSON CONTROLS 148 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 149: ...JOHNSON CONTROLS 149 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 150: ...JOHNSON CONTROLS 150 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 151: ...JOHNSON CONTROLS 151 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 152: ...JOHNSON CONTROLS 152 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Страница 153: ...JOHNSON CONTROLS 153 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Страница 154: ...JOHNSON CONTROLS 154 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...