13
2
JOHNSON CONTROLS
FORM 145.05-NOM2 (807)
APPROVALS
Designed certified by ETL for indoor installation
only.
LIMITATIONS
The installation of this unit must conform to local
building codes as well as the National Electrical Code
ANSI/NFPA No. 70 – latest edition.
Refer to Table 2 for voltage limitations and Table 3 for
operating limitations.
If the VAV boxes in the conditioned
space have hydronic heating coils
installed, it is the responsibility of the
installing contractor to take appropri-
ate measures to protect the hydronic
coils against low unit supply air tem-
peratures that could result in the freeze
up and rupture of the coils.
UNIT INSPECTION
Immediately upon receiving the unit, it should be
inspected for possible damage which may have
occurred during transit. If damage is evident, it should
be noted on the carrier’s freight bill. A written request
for inspection by the carrier’s agent should be made at
once.
See “Instruction” manual Form 50.15-NM for
more information and details.
To ensure warranty coverage, this
equipment must be commissioned
and serviced by an authorized YORK
service mechanic or a qualifi ed ser-
vice person experienced in packaged
rooftop installation. Installation must
comply with all applicable codes, par-
ticularly in regard to electrical wiring
and other safety elements such as relief
valves, HP cut-out settings, design
working pressures and ventilation re-
quirements consistent with the amount
and type of refrigerant charge.
Lethal voltages exist within the control
panels. Before servicing, open and tag
all disconnect switches.
TABLE 2 – VOLTAGE LIMITATIONS
UNIT POWER SUPPLY
VOLTAGE VARIATIONS
MINIMUM VOLTS
MAXIMUM VOLTS
208-3-60
180
228
230-3-60
207
253
480-3-60
415
506
575-3-60
518
632
TABLE 3 – OPERATING LIMITATIONS
MINIMUM
MAXIMUM
ENTERING AIR COIL - DRY
BULB
68.0
°
F
90.0° F
ENTERING AIR COIL – WET
BULB
57.0° F
72.0° F
COOLING COIL AIRFLOW
VELOCITY
400
FPM
600
FPM
STEAM HEAT – STEAM
PRESSURE
5 PSIG
15 PSIG
STEAM HEAT STEAM FLOW
RATE (LB/HR)
HOT WATER HEAT ENTERING
WATER TEMP
140° F
160° F
HOT WATER HEAT WATER
FLOW RATE
SECTION 2 – INSTALLATION
Содержание YSCD
Страница 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...
Страница 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM2 807 Service FIG 12 WIRING DIAGRAM MAIN CONTROL BOARD LD13010 ...
Страница 107: ...107 JOHNSON CONTROLS FORM 145 05 NOM2 807 8 FIG 13 WIRING DIAGRAM EXPANSION CONTROL BOARD LD13011 ...