If Supply Air Temperature Control and Dew Point
Control are selected, it will pick the higher of the two
outputs to control the economizer water valve.
If Return Air Temperature Control and Dew Point
Control are selected, it will pick the higher of the two
outputs to control the economizer water valve.
If Supply Air Temperature Control, Return Air
Temperature Control, and Dew Pont Control are
selected; the Unit Control will compare the Supply
Air Temperature Control output to the Return Air
Temperature Control output and select the lower of
the two outputs. It will then compare it to the Dew
Point Control output and select the higher of the two
values.
The 0 to 10 volt analog output is located at the AO-1
terminals 1 and 2 and is used to control the outdoor
and return damper motor. As long as the outdoor air
economizer is enabled and the unit Air Flow Switch is
closed, the output will never be less than the
“O/A MIN
POS”
setting.
COOLING OPERATION
The following parameters must be programmed through
the
“Setpoints”
section of the Keypad / Display or by
a communicated input.
“AC-S/A TEMP EN”
– The unit can control the
operation of the cooling function by either the supply
air temperature or the return air temperature. If supply
air control is desired, this value must be turned ON. ON
is the default value.
“AC / ECON S/A SP”
– This is the set point the
controller will control to if the unit is confi gured for
“AC-S/A TEMP EN”
, the default value is 55.0° F.
“AC-R/A TEMP EN”
- The unit can control the
operation of the cooling function by either the supply
air temperature or the return air temperature. If return
air control is desired, this value must be turned ON.
OFF is the default value.
“AC / ECON R/A SP”
– This is the set point the
controller will control to if the unit is confi gured for
“AC-R/A TEMP EN”
, the default value is 75.0° F.
Sequence of Operation
Supply Air Temperature Control
The cooling will be enabled when the supply air
temperature is 5.0° F greater than the
“AC / ECON S/A
SP”
set point. Cooling will be disabled when the supply
air temperature is 10.0° F less than the
“AC / ECON
S/A SP”
set point. The control waits fi ve minutes from
the time the supply air temperature drops 10.0° F below
the set point before it disables the cooling.
The control compares the supply air temperature to
the
“AC / ECON S/A SP”
set point and generates a
variable percentage output based on the difference and
the amount of change in the supply air temperature to
a change in output. This output is used to modulate the
chiller water coil valve actuator.
Return Air Temperature Control
When the unit is under Return Air Temperature
Control, the cooling will be enabled when the return air
temperature is 2.0° F greater than the
“AC / ECON R/A
SP”
set point. Cooling will be disabled when the return
air temperature is 0.5° F less than the
“AC / ECON R/A
SP”
set point. The control waits fi ve minutes from the
time the return air temperature drops 0.5° F below the
set point before it disables the cooling.
The control compares the return air temperature to the
“AC / ECON R/A SP”
set point plus 1.0° F and generates
a variable percentage output based on the difference and
the amount of change in the return air temperature to a
change in output. This output is used to modulate the
chiller water coil valve actuator.
Dew Point Temperature Control (FlesSys Units)
In addition to Supply Air Temperature Control and
Return Air Temperature Control, Dew Point Temperature
Control can also be selected on FlexSys units. The Unit
Control compares the derived Dew Point Control set
point and the dew point of the supply air; and generates
an analog output based on the difference and the amount
of response to a given change in output.
Sequence of Operation
Содержание YSCD
Страница 10: ...10 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...38 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 46: ...46 JOHNSON CONTROLS FORM 145 05 NOM2 807 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...105 JOHNSON CONTROLS FORM 145 05 NOM2 807 LD13009 8 FIG 11 WIRING DIAGRAM POWER CIRCUIT ...
Страница 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM2 807 Service FIG 12 WIRING DIAGRAM MAIN CONTROL BOARD LD13010 ...
Страница 107: ...107 JOHNSON CONTROLS FORM 145 05 NOM2 807 8 FIG 13 WIRING DIAGRAM EXPANSION CONTROL BOARD LD13011 ...