![background image](http://html1.mh-extra.com/html/york/yhau-ce/yhau-ce_installation-operation-and-maintenance_3511378020.webp)
JOHNSON CONTROLS
20
FORM 155.35-ICOM2.EN.CE/GB (1018)
DATE: 10/30/2018
SECTION 2 – PRODUCT DESCRIPTION
LOW TEMPERATURE GENERATOR
The low temperature generator is a falling liquid film
type where the hot refrigerant from the high tempera-
ture generator heats the dilute solution. The refrigerant
vapor from the high temperature generator then con-
denses into liquid and flows to the condenser.
LD26807
Low Temp.
Generator
CONDENSER
The refrigerant vapor from the low temperature gener-
ator as well as the condensed refrigerant from the high
temperature generator enter the condenser. There, they
condense into a liquid state using the cooling (condens-
er) water from the absorber section. The cooled refrig-
erant is sent to the bottom evaporator section through a
U-pipe (liquid seal). This completes the cooling cycle.
LD19880_a5
Condenser
Cooling Water Outlet
Concentration
Solution In