SECTION 8 – TROUBLESHOOTING
If the chiller-heater malfunctions while it is operating,
it is imperative to find and correct the problem. If the
cause is not clear, and performing a countermeasure
does not fix the problem, or if the chiller-heater seems
to have a serious problem, contact your local Johnson
Controls Service Center immediately. If the chiller-
heater stops because of a problem, wait until the chilled
/hot water pump, cooling water pump, and chiller-heat-
er unit stop. Then, take the following actions.
Several items should be checked routinely whenever
the chiller-heater experiences any problems.
• Open the main valve.
• See if the valves of the chilled / hot water system
and cooling water system are correctly opened and
the specified flow rate is secured.
• See if the cooling tower is operating normally.
• Check the valves and pumps of the cooling water
system and confirm that the specified flow rate is
secured.
Contact your local Johnson Controls Service Center if
any of the following situations appear:
• The setting of the water flow rate is unknown.
• It takes 30 minutes or more to restore operations.
• Solution is crystallized.
• The cause of the trouble is not readily apparent.
Check the causes in order. Any of these
causes will start the automatic dilution
operation, then stop the chiller-heater.
Check that the diluting operation was
completed. If it is not, dilute the solution
according to the Manual Refrigerant
Blowdown and Dilution Method on page
TABLE 27 -
TROUBLESHOOTING THE HIGH TEMPERATURE GENERATOR
ITEM
CAUSE
COUNTERMEASURE
1
Cooling water is low or not
flowing.
See if the cooling water supply rate matches the specification. (Check the flow
meter, discharge pressure of the cooling water pump, current, and other pertinent
flow gauges.) If the flow rate is low, check the opening ratio of the flow controller
valve and check the strainer for clogs.
2
Cooling water temperature
at inlet is high.
Check the performance of the cooling tower.
3
Non-condensable gas stays
in the machine.
• Check the capacity of the vacuum pump.
• Check the purge unit. Purge air from the chiller-heater See
. If partial load operation is continued for a long period, non-
condensable gas tends to stay in the absorber. In this case, purge directly from
the absorber. Use the instructions in
4
Heat exchange tube is dirty
(chilled / hot water, cooling
water).
Contact your local Johnson Controls Service Office.
5
Solution is crystallized.
6
Corrosion inhibitor is worn.
7
Air leaks in absorption
chiller-heater.
Содержание YHAU-CE
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 84: ...JOHNSON CONTROLS 84 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...